taBle 2. aDvanceD conFIGUratIon (cont.)
menU
FeatUre
Keypad Lockout
340
Enable Pin Access
341
Set PIN Access
342
Code
Fan Mode
350
Enable
System Mode
360
Enable
Minimum Deadband
3-10°F, 1.5-5°C
380
Adjustment
Pre-Occupancy
390
Purge
Maximum Override
0=Time until next
395
Time Limit
Cycles Per Hour
400
(CPH)
Cooling Stage 1
Cycles Per Hour
410
(CPH)
Cooling Stage 2
Cycles Per Hour
420
(CPH)
Heating Stage 1
Cycles Per Hour
430
(CPH)
Heating Stage 2
Cycles Per Hour
450
(CPH)
Heating Stage 3
Heat Recovery Rate
460
Cool Recovery Rate
470
Minimum Off Time
480
Humidity Control
490
Enable
(Select models only)
Programmable/
500
Intermittent Fan
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
oPtIons
stD.moDel
DeFaUlt
0-3
0
0,1
0
000-999
000
1-3
3
0-3
1
3°F
0-3 hours
0 hours
3
event; or
1-4 hours
0-6 CPH
3 CPH
0-6 CPH
3 CPH
0-12 CPH
5 CPH
0-12 CPH
5 CPH
0-12 CPH
5 CPH
0-18°F/Hr
5°F/Hr
0-10°C/Hr
0-18°F/Hr
5°F/Hr
0-10°C/Hr
1-10 minutes
4 minutes
0-2
0
DescrIPtIon / comments
Restricts access to certain features of device; Service Menu still available if enabled.
0 =
No key pad lockout (Default)
1 =
Disables Schedule and System keys
2 =
Disables Schedule, System, and Fan keys
3 =
Disables all keys
Applies a 3 digit access code to enter Service Menu 342
0 =
Disable,
1 =
Enable
Choose a 3-digit code.
1 =
ON: Fan is turned on regardless of demand.
2 =
Auto: Fan is turned on according to heating or cooling demand.
3 =
ON or Auto: Allows occupant to select either 1 or 2 above.
Allows ability to determine which system modes the occupant can select.
0 =
OFF, Auto
1 =
OFF, Heat, Cool, Auto
2 =
OFF, Heat, Cool
3 =
Heat, Cool, Auto
Select a changeover deadband value to prevent short cycling between heating and cooling modes.
The value is adjustable to meet various HVAC system requirements.
Select to energize fan for selected number of hours (0-3) prior to all occupied events.
Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum
amount of time as defined in this Service Menu.
0 =
Remainder of time until the next scheduled event.
1 =
1 Hour
2 =
2 Hours
3 =
3 Hours
4 =
4 Hours
Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for
Stage 1 cooling.
Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for
Stage 2 cooling.
Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for
Stage 1 heating.
Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for
Stage 2 heating.
Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for
Heating Stage 3.
Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp
recovery.
Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp
recovery.
Sets the minimum off time for both the heat and cool output.
Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes
dehumidify.
0 =
Disabled
1 = Dehumidify Control
0 =
Disable
1 =
Programmable Fan: Fan operates continuously in occupied periods or with demand in
unoccupied periods.
2 =
Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.
7
P/N 70476 3220-2265 REV 01