USERS GUIDE FOR S300RPTU REMOTE PROGRAMMING TEST
TOOL AND S300SAT SATELLITE RELAY DEVICE
Figure 1: S300RPTU
5
8
INTRODUCTION
The S300RPTU Remote Programming and Test Tool is designed for communication with System
Sensor 300 series detectors, permitting access to various functions and logs within the detectors.
Communication is achieved through the detector's indicator LED, and uses one of two methods:
1.
Via an LED and Opto-diode built in to the S300RPTU, for close range (approximately 30mm)
communication. This allows direct communication via the detector LED indicator.
2.
Using radio communication via an S300SAT which can be clipped to the detector using
proprietary access poles, allowing a range up to 4.5m.
The S300RPTU is a menu driven device. With reference to figure 1, the controls for navigating
through the menus are as follows:
(1)
On/Off Switch
(2)
Up/Down Arrows - to scroll through menus
(3)
OK button - Select required function
(4)
Esc - Returns to the previous menu
POWER ON
When the S300RPTU is turned on, the screen shown left will be
Series 300
displayed for approximately 5 seconds, and then will be replaced by
RPTU - v.1.5
the first of the main menu screens.
*** READY ***
MAIN MENU
There are six main menu items as follows:
ACQUIRE
1
Reads the settings previously programmed into the detector being
accessed including sensitivity, address, device type, LED operation
Detector
and service date. Refer to section 2.
Settings
Last
2
Displays the information acquired from the last detector read. Refer
Detector
to section 2.
Read
Write
3
Programmes new settings such as address, sensitivity and mode of
Detector
LED operation into the detector. Refer to section 3.
Settings
Checks that maintenance has been satisfactory, and if OK
Write
4
programmes the current date into the detector as the new service
NEW
date. Refer to section 4.
Service Date
Alarm
5
Performs a detector Alarm Test. Refer to section 5.
Test
Press OK x 2
Allows the user to set the S300RPTU tool to suit requirements,
RPTU
6
including the tool operating language and communication method.
Settings
Refer to section 1.
D300-03-00
4
3
Esc
Ok
6
7
Figure 2: S300RPTU
Batteries
3 x 1.5V LR03 (AAA)
Batteries Required.
1: S300RPTU AND S300SAT SET UP
Prior to any communications with detectors, it is necessary to configure the S300RPTU and
S300SAT. This procedure should only need to be carried out once, the settings then being retained
until changed via this screen.
1
During the set-up procedure, ensure that only one S300RPTU and S300SAT pair are switched on
within a 10m area.
Switch on both the S300 RPTU and S300SAT. Scroll down through the main menu screens to select
"RPTU Settings". This gives access to set-up screens as follows:
RPTU
Settings
LCD
Intensity
RPTU
2
Set LINK
mode
Read
Current
Date
Set
RPTU
Language
Set
S300SAT
Address
Note that only one new setting can be made each time the RPTU settings screen is accessed. For
each new setting, the S300RPTU will display the ready screen as follows for a few seconds, then
*** Ready ***
2: ACQUIRE DETECTOR SETTINGS AND LAST DETECTOR READ
Except where indicated, the same operating screens apply to both acquisition of the detector settings
and the display of information from the last detector read:
ACQUIRE
Detector
Settings
OK
Attempting
Connection
LINK?...>END
Detector Data
Corrupted
Esc
Detector Data Corrupted,
Return detector to supplier
for reprogramming.
Device is:
conventional
Type - -
Class:
------------
Detector
Device
Address
XX
% Dirty
1234567890
The S300RPTU will automatically display the relevant screen. In normal conditions
with no smoke present, the "% Dirty screen" will be displayed, giving an indication of
the level of contamination in the detector chamber. If the detector has reached it's drift
compensation limit and needs cleaning the "Sensor Contaminated" screen will be
shown, and if faulty the "Chamber Faulty" screen will be shown.
Reading
Optical
XX %
Thermal
XX %
Continued overleaf
6
Use the up/down arrow buttons to adjust
OK
6.1
screen intensity to suit then press OK to
1234567
confirm setting
Use the up/down arrow buttons to display
6.2
Set
either communication via the RPTU LED or
Link Via
the S300SAT, then press OK to confirm
S300SAT
setting.
Date is displayed as -
6.3
Current Date
Day/Month/Year
dd/mm/yy
(Based on GMT) Press OK to confirm
Use the up/down arrows to display the
6.4
Language
required language to be used by the
set to:
S300RPTU, and then press OK to confirm
English
setting
The S300SAT can be set to one of 16
addresses to prevent cross talk if more than
6.5
SAT Address
set to:
one is to be used on a site. Use the up/
XX
OK
down arrows to select the relevant address
(00-15) then press OK to confirm setting.
return to the "RPTU Settings" screen.
The exception to this is the S300SAT address screen, where the RPTU
will briefly display "Attempting Connection" before the ready screen
appears.
1
OK
Connection
failed
Esc
** Retry? **
Device
Information
Missing
Esc
Detector incompatible
with S300RPTU.
Displays Detector Type Code:
A = Conventional EN54 Standard,
B = Conventional NF (AFNOR),
C = Special
Displays Detector Type:
Thermal, Optical or Opto-Thermal
Displays Detector Address
(00 to 99)
Sensor
Chamber
CONTAMINATED
FAULTY
Service
Replace Unit
Displays the current Chamber / Sensor values. For an optical or thermal
detector, the optical or thermal sensor reading only will be displayed as
applicable. For photo-thermal detectors both readings will be shown.
Last
2
Detector
Read
OK
Note:
1.
Last Detector Read
Detector information is only
displayed if a successful
"Aquire Detector Settings"
has previously been run.
2.
When the S300RPTU is
switched off, the Last
Detector Read data is lost.
Service information - This
screen is only displayed
for Optical and Photo-
Thermal detectors.
I56-1720-004EN

Publicidad

Tabla de contenido
loading

Resumen de contenidos para System Sensor S300RPTU

  • Página 1 Note that only one new setting can be made each time the RPTU settings screen is accessed. For each new setting, the S300RPTU will display the ready screen as follows for a few seconds, then return to the “RPTU Settings” screen.
  • Página 2 To prevent cross communication where more than one unit is in use on a single site, the S300SAT and established, or communications have been interrupted during transmission of the new S300RPTU may be set to an address for 00 to 15 - See RPTU setup for details. settings. Connection should be re-attempted by pressing OK.
  • Página 3: Menu Principale

    Nota: durante la procedura di configurazione, assicurarsi che nel raggio di 10 metri non ci siano altre unità S300RPTU o S300SAT accese. Accendere l'S300RPTU e l'S300SAT. Selezionare la voce "Config. RPTU" del men ù principale. Si ottiene accesso alle seguenti schermate: Figura 1: S300RPTU Config.
  • Página 4 300 distante fino a 8 m circa. L'S300SAT si aggancia direttamente al in Corso" viene visualizzata per alcuni secondi, l'indicatore a barra esprime rivelatore e può essere fissato su pali di estensione System Sensor oppure, attraverso un adattatore, l'avanzamento dell'operazione. Al termine della programmazione, l'S300RPTU ritorna a quelli della No Climb Products.
  • Página 5: Introducción

    ...?...>FIN *Reintente?* patentado, incrementar la distancia hasta 4,5 m. El S300RPTU es un equipo con menús de control. Con referencia a la figura 1, los controles de navegación para desplazarse por los menús son los siguientes: Pérdida Base de datos Interruptor de On/Off (Encendido/Apagado) Información...
  • Página 6: Escribir Configuración Del Detector

    Para evitar cruces en las comunicaciones cuando se utiliza más de una unidad en un único recinto, el S300SAT y el S300RPTU se pueden ajustar a una dirección entre 00 y 15. Véase el apartado sobre nuevos ajustes. Intente conectar de nuevo pulsando la tecla OK.
  • Página 7 Daten. Die Kommunikation erfolgt über die eingebaute Melder-LED und ist eine von den zwei Möglichkeiten: Verbindungs- Keine Im Nahbereich (ca. 30mm) über die LED und Photodiode des S300RPTU und der im Melder aufbau? Verbindung! eingebauten Anzeige-LED …> ENDE Nochmal? Im Fernbereich (bis ca.
  • Página 8: Weitere Displayanzeigen

    Hinweis: Vergewissern Sie sich, dass während der Konfigurationseinstellung nur ein Paar des wechselt die Displayanzeige des RPTU zu "Start Übertragung Neue Werte". S300RPTU UND S300SAT innerhalb eines Wirkungsbereiches von 10 m mit der gleichen Adresse Erscheint stattdessen "Keine Verbindung! Nochmal?" konnte entweder die (00-15) aktiv ist (siehe RPTU Einstellung).
  • Página 9: Mise Sous Tension

    Avant toutes utilisations, S300RPTU et S300SAT doivent êtres configurés. Les données configurées sont conservées en mémoire jusqu'à une nouvelle configuration. Note: Pendant la configuration, vérifiez qu'il n'y a pas plus d'un S300RPTU et d'un S300SAT en service dans une zone de 10 m.
  • Página 10: Écrire La Nouvelle Date De Sav

    7 : S300SAT l'écran " début transmission des données". S300SAT assure une liaison par fréquence r a dio entre S300RPTU et un détecteur sur des distances Si l'écran "Echec de la connection * réessayer *" apparaît, soit la communication n'a allant jusqu'à...
  • Página 11: Главное Меню

    РУКОВОДСТВО ПО ИСПОЛЬЗОВАНИЮ 1: УСТАНОВКИ МПДУ И ИКР МНОГОФУНКЦИОНАЛЬНОГО ПУЛЬТА ДИСТАНЦИОННОГО Установки МПДУ сохраняются при выключении питания. В МПДУ, поставляемых в Россию, по умолчанию установлен русский язык и вид связи - с МПДУ. УПРАВЛЕНИЯ И ИНФРАКРАСНОГО РЕТРАНСЛЯТОРА РЕЖИМЫ При помощи кнопок st МПДУ выберите меню 6 и РАБОТЫ...
  • Página 12 ИКР обеспечивает связь МПДУ с датчиками установленными на высоте 4,5 метров. ИКР ДАННЫЕ ДАННЫЕ СОЕДИНЕНИЕ устанавливается на извещатель при помощи телескопической штанги ХР-3 System Sensor. Для В ДАТЧИКЕ ОТСУТСТВУЮТ ПРЕРВАНО исключения перекрестной трансляции при одновременном использовании нескольких ИКР , в...

Este manual también es adecuado para:

S300sat

Tabla de contenido