1
About this manual
Manual code: DCMIIN1PIFM2L
Version: 1.30
2

General Description

All the peripheral devices of the system must be connected in parallel to the loop circuit (2 pole shielded cable).
The control panel communicates with the loop devices via a digital protocol which allows their complete
control. The loop utilizes the same two wires for the power supply to devices and for two-way communication.
Each IFM2L module contains circuits for the management of two loops. Previdia Max control panels are
capable of managing up to 16 loops through a maximum of 8 IFM2L modules.
IFM2L comes with:
• 3 screws for securing the module to the grounding bar
• Instructions manual
Figure 1 - IFM2L, page 1
[A]
Status LED
[B]
Mini USB port
Loop A connection
[C]
Loop-A
Loop-B connection
[D]
Loop-B
[E]
Holes for the grounding bar screws
[F]
CAN drive connector (opposite)
LED IFM2L
CAN
RXA
TXA
RXB
TXB
About this manual
Maximum number of devices managed
terminals
terminals
Consumption @
Colour
Blue
Green
Red
Green
Red
IFM2L module - technical specifications
Power supply voltage
Operating temperature
by a loop
stand-by
27.6V
maximum
Maximum voltage on Loop-A
Maximum voltage on Loop-B
On solid / Flashing
Activity on the CAN communication BUS
Reception activity - receiving data from devices on loop A
Transmission activity - transmitting data to devices on loop A
Reception activity - receiving data from devices on loop B
Transmission activity - transmitting data to devices on loop B
19-30 V
supplied by IFM24160 module
from -5°C to +40°C
240
35mA
50mA
0.5A
0.5A