ADVANCE-GRP
2. COMPLIANCE WITH STANDARDS
The interlocked sockets of the ADVANCE-GRP Series are intended for use in Zone 21 (EN 60079-0:2012+A11:2013, EN
60079-31:2014).
3. TECHNICAL DATA
3.1 TYPE OF EX PROTECTION
: II 2D Ex tb IIIC T90°C Db IP66
Ta -25/+60°C
Year xxxx: year of manufacture.
: Product suited for use in explosive atmosphere.
II: Product classified as belonging to group II, installable in above-ground systems.
2D: Product classified as belonging to category 2 for environments featuring the presence of combustible dust (D) suited for
installation in Zone 21.
Ex tb: protection mode (protection by means of enclosure).
IIIC: Equipment classified as group IIIC, product suited to be used in presence of conductive dust.
T90°C: Maximum surface temperature value.
Ta -25/+60°C: Allowed room temperature range, present at the installation site.
Db: Equipment Protection Level (EPL).
3.2 EC TYPE TEST CERTIFICATE
IMQ 11 ATEX 010
3.3 DEGREE OF PROTECTION OF THE INTERLOCKED SOCKET IP66
3.4 POWER SUPPLY TERMINALS, CONNECTING CONDUCTORS, TIGHTENING TORQUES AND DRAWABLE CURRENTS
Socket
16A
32A
63A
Terminal section.
Rated
current
16A
32A
63A
Drawable currents and cable temperature
(*) Provide a power supply cable suited for the maximum entry temperature.
4. INSTALLATION
The installation must be carried out by suitably trained and skilled personnel in compliance with applicable laws. Plant-
engineering standards for environments classified against the risk of explosion due to the presence of combustible dust
must be observed (for example: EN 60079-14, or other national regulations/standards).
Comply with generally accepted rules of behaviour for installation of electrical materials, with national accident-prevention rules
and with the safety instructions contained in this manual whenever you work on the unit. Do not open the energized enclosure or
make sure the atmosphere is not dangerous. Before you open the cover of the interlocked socket, wait 15 minutes after cutting
out the power supply.
MP36510
Stranded
Flexible
4mm²
10mm²
25mm²
Maximum drawable current
Ta 40°C
Ta 50°C
-
-
55A
4mm²
10mm²
25mm²
Ta 60°C
-
-
50A
12
Cable temperature
16A
25A
45A
85°C (*)
-
-
ZP90767-6