Maintenance And Cleaning - D+H CDC 200/350-BSY+ Manual Original

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Functional description
A CDC -BSY+ synchronous group can contain up to
8 drives, which communicate via bus. Each drive has
its own address, configurable with SCS.
The last drive of a synchronous group is the master,
which controls the other drives, the slaves.
Differences in forces between the drives of a group
are balanced by means of intelligent force and
position control. In the event that a drive
malfunctions, all the drives are automatically cut off.

Maintenance and cleaning

Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be carried
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Declaration of Conformity
We declare under our sole responsibility that the
product described under "Technical Data" is in
conformity with the following directives:
2004/108/EG, 2006/95/EG
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Thomas Kern
Member of the Board
12.06.2010
99.823.67 2.5/11/13
Maik Schmees
Authorized signatory, Technical Director
Troubleshooting
Visual inspection:
Only one master drive is allowed.
The master always has the last address of all the
drives; this can be found on a sticker attached to
the drive. Slaves are numbered downwards from
the master, so that in a group of three drives, for
example, the master is no. 3, with a slave 2 and
slave 1 drive. Please note that this only applies in
the ex-factory configuration. As soon as the drives
are reconfigured with SCS, the ex-factory
addressing no longer applies.
Wiring:
Is the group wired correctly?
Please refer to the connection diagrams in this
regard.
Adjustment of zero point:
Adjust the zero point.
Software SCS or the special magnet
MAG 502 is required.
Call D+H Service:
Drives must be configured.
Software SCS is required.
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
Disposal
Electrical devices, accessories and packaging
should be sorted for environmental-friendly recycling.
Do not dispose electrical devices
into household waste!
Only for EC countries:
According the European Guideline
2002/96/EG for waste electrical and
electronic equipment and its implemen-
tation into national right, electrcal
devices that are no longer usable must be collected
separately and disposed of in an environmentally
correct manner.
English
CDC 200/350 (-SBD)-BSY+
9/20

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cdc 200/350-sbd-bsy+Cdc 200/600-bsy+Cdc 200/600 -sbd-bsy+

Tabla de contenido