Operation

WIRELESS LOCAL MONITOR GENERAL OPERATION

The normal state of the display unit is to have no lights active. This indicates that the
generator has no problems. When any problems occur, the lights will indicate the problem
based on the information in this section.

GENERATOR TRANSCEIVER STATUS LIGHT

The generator transceiver has a green status light that indicates it has power and is communicating
with the display unit. This light can be viewed inside the generator compartment, through the wire
loom opening when the generator lid is raised.
• Solid light Green light - power present / communication established
• Flashing Green light - power present / no communication

DISPLAY UNIT GREEN LIGHT (GENERATOR OK OR RUNNING)

During normal operation, if the generator is in AUTO mode and does not have any maintenance
actions, warnings or alarms active, no lights will be illuminated.
To verify the status of the generator, the Test button can be pressed to show the status. If the
generator is set to AUTO mode and no alarms or warnings are present, the green light will illuminate
when the Test button is pressed.
The green light will flash every five (5) seconds when the generator is running either in AUTO or
MANUAL mode.

DISPLAY UNIT YELLOW LIGHT (MAINTENANCE NEEDED OR WARNING ACTIVE)

The yellow light indicates either:
• Generator warning is present
• Generator maintenance is required.
The generator will not be prevented from running when the yellow light is on.
When active and the generator is not running, the yellow light will flash once every five (5) seconds.
If the generator is running with a yellow light active, both the green and yellow lights will flash once
every five (5) seconds.
The internal buzzer will sound once every four (4) hours for one (1) second when the yellow light is
active. During a period of inactivity, the buzzer may be silenced by briefly pressing and releasing the
Test button; the buzzer will pulse twice to indicate it has been silenced. The buzzer will not reactivate
until a new alarm has been detected.
NOTE:
If the button is pressed while the buzzer is sounding, it may not be silenced.