LED
26 mm
(Hidden)
76 mm
8.4 mm
M200WC-RF interface status LED
Status
LED State
Green pulse Device OK and connected
Power-on initialisation
Amber ON
Fault
Amber blink Device has an internal trouble
Serial (USB)
Green blink
communication
RF communication
Blue blink
Patents Pending
EU Declaration of Conformity
Hereby,
Life Safety Distribution GmbH declares
that the radio equipment type
is in compliance
The full text of the EU DoC can be requested from:
HSFREDDoC@honeywell.com
M200WC-RF[-PRO]
RADIO SYSTEM USB INTERFACE
INSTALLATION AND USER INSTRUCTIONS
96 mm
USB Connector
- Type A
13 mm
50°C
0°C
Meaning
Device OK but not recognized
Interface is receiving data from
the PC application
Interface is receiving data from
an RF device
M200WC-RF[-PRO]
with directive 2014/53/EU
Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy
DESCRIPTION
The M200WC-RF[-PRO] is an interface that connects to a PC
through a USB port and allows communication with System Sensor
200 Series Commercial RF devices. The M200WC-RF[-PRO] is
31 mm
powered directly by the USB port.
This radio device complies with the requirements of 2014/53/EU
for conformance with the RED directive.
SPECIFICATIONS
Supply Voltage:
Supply Current:
USB standard:
USB connector:
Radio Frequency:
RF Output Power:
Range:
Relative Humidity:
INSTALLATION
The M200WC-RF[-PRO] has an adjustable USB connector in order
to maximize the RF coupling with radio communicating devices,
and to change its profile when connected to a portable PC.
Do not connect the M200WC-RF[-PRO] interface until the
correct drivers have been installed on the target PC.
Download the latest version of the AgileIQ
(with the correct interface drivers) from a trusted source - see the
Radio Programming and Commissioning Manual for the installation
procedure.
Only plug the RF interface into a spare USB port on the PC
when requested.
Note that when the interface is attached, Windows may take a
number of seconds to recognize the new hardware correctly;
always wait a short period for the LED to change from yellow
to green before proceeding with any other operation.
LED INDICATORS
The interface is equipped with an RGB LED, giving an indication of
power and communication (both RF and USB) status (see table).
PROGRAMMING
Used in conjunction with the AgileIQ
the RF interface is used to program and communicate with System
Sensor 200 Series RF fire detection devices. For information on
setting-up, commissioning and monitoring an RF mesh network,
see the Radio Programming and Commissioning Manual - ref.
D200-306-00.)
NOTE: Do not run more than one interface at a time to
commission devices or carry out a site survey in an area.
I 56- 4157- 003
4.3 – 5.5V Direct Current (DC)
33mA typical @ 5VDC
USB 2.0 (full speed)
Type A
865-870 MHz;
13 dBm (@ 5VDC)
130m (typ. in free air)
10% to 93% (non-condensing)
radio interface software
®
Device Interface Software,
®
E N G L I S H
I56-4157-003