READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS
CAREFULLY BEFORE INSTALLING AND SAVE IT FOR FUTURE USE
General Features
The TM-2100 series of Room Command Modules is designed to provide room
temperature sensing in fan coil operations and allows the user a local room temperature
setpoint adjustment. Some models provide fan speed override.
The setpoint range is 12 to 28 °C or +/- (range +/- 3 °C), depending on the model
(see "Ordering Codes").
Several models permit the user to override the Command Mode from Unoccupied
(LED off) to Temporarily Occupied (LED on) by pressing the "Occupancy" button
(shown in Figure 1) on the side of the module.
The devices are designed for wall mounting in the room to be controlled. It should be
located where the occupant can easily read and adjust the set point dial or fan speed
override switch. It should be placed where the temperature is representative
of the general room conditions. Cold or warm air draughts, radiant heat and direct
sunlight should be avoided.
The TM-2100 series of Room Command Modules is designed to be used as an input
to a DDC terminal unit controller, primarily for the FCC series, and field controller from
the Facility Explorer series.
Figure 1:
Dimensions in mm
(a). 3-Speed Fan Override dial
(b). Temperature Setpoint dial
(c). Occupancy Button
(d). Mode LED
Mounting
Tools
• Flat-head screwdrivers (3 mm and 5 mm) or special tool to open module
(available from Johnson Controls, Code Number: TM-9100-8900).
• Drill, bits and appropriate 4 mm screws and plugs.
Figure 2:
Removing cover from base
(a). Insert the screwdriver (or special Johnson Controls tool
TM-9100-8900) into the gap at the center top of the cover.
(b). While pressing down gently, prise the base away from the cover.
As the two parts separate, remove the tool and continue to pull the
cover away from the base until the cover is free.
Figure 3:
Module Base
Mount the base on the wall and secure it with at least two screws.
Before piercing the wall it is recommended to cover the escapes of cables.
Wiring
• In order to prevent damages to the equipment and in order to avoid electric shocks,
before connecting or disconnecting any wires, ensure that all power supplies have
been switched off and that all the cables are potential free.
• The installation of electrical wiring must conform to local, national, and regional
regulations and should be carried out by authorized personnel only.
• Users should ensure that all Johnson Controls products are used safely and without
risk to health or property.
• Terminations are made on the terminal blocks in the base of the module, which accept
2
up to 1.5 mm
(1 x 14 AWG / 2 x 18 AWG) wires.
• All wiring to the module is at extra low (safe) voltage and must be separated
from power line voltage wiring.
• Do not run wiring close to transformers or high frequency generating equipment.
• Complete and check all wiring connections before applying power to the system
to which the module is connected.
WARNING: The circuits in the module are sensitive to static electricity.
Take suitable precautions.
Figure 4:
TM-2140-0000 Wiring - FCC Series / FX Series
Figure 5:
TM-2140-0000 Wiring - FX03
Figure 6:
TM-2150-0000 Wiring - FCC Series / FX Series
Figure 7:
TM-2150-0000 Wiring - FX03
Figure 8:
TM-2160-0000 - TM-2160-0005 Wiring - FCC Series / FX Series
Figure 9:
TM-2160-0000 - TM-2160-0005 Wiring - FX03
Figure 10: TM-2160-0002 - TM-2160-0007 Wiring - FCC Series / FX Series
Figure 11: TM-2160-0002 - TM-2160-0007 Wiring - FX03
Figure 12: TM-2190-0000 - TM-2190-0005 Wiring - FCC Series / FX Series
Figure 13: TM-2190-0000 - TM-2190-0005 Wiring - FX03
1
TM-2100
Ordering Codes
Code Numbers
Descriptions
TM-2140-0000
Room Sensor, Temperature Output only
TM-2150-0000
Room Command Module with "Occupancy" Override
TM-2160-0000
Room Command Module with "Occupancy" Override and Setpoint Adjustment (12...28° C)
TM-2160-0005
Room Command Module with "Occupancy" Override and Setpoint Adjustment (+/-)
Room Command Module with "Occupancy" Override and Setpoint Adjustment (12...28° C)
TM-2160-0002
and 3-Speed Fan Adjustment
Room Command Module with "Occupancy" Override and Setpoint Adjustment (+/-)
TM-2160-0007
and 3-Speed Fan Adjustment
TM-2190-0000
Room Command Module with Setpoint Adjustment dial (12...28° C)
TM-2190-0005
Room Command Module with Setpoint Adjustment dial (+/-)
Accessories
TM-1100-8931
Surface Mounting Base - White
TM-9100-8900
Special tool to open module

Technical Specifications

Product Codes
TM-2100 Series - Room Command Module
Supply Voltage
5 VDC from controller
Ambient Conditions
- Operating
0 to 50° C - 10 to 90% RH (non condensing)
- Storage
-20 to 70° C - 10 to 95% RH (non condensing)
Temperature
- Sensor
NTC Thermistor 0 to 50° C - 10 kOhm at 25° C
- Set point override
10 kOhm potentiometer marked for 12 to 28° C or +/-
Three-Speed Fan
10 kOhm potentiometer with mechanically guided positions for Auto, Off, 1 (low speed),
Override
2 (medium speed) and 3 (high speed)
Occupancy Button
Momentary contact (switches 5 V at 1 mA)
Mode Indicator
Green LED (5 V, 4 mA)
Dimensions
TM-2140 / TM-2150: 80 x 80 x 32 mm
(H x D x W)
TM-2160 / TM-2190: 80 x 80 x 35 mm
Housing Material
ABS + PC, self-extinguishing HB UL94
Housing Protection
IP 30 (EN 60529)
Weight
0,15 Kg
Directive: 89/336/EEC - EN 61000-6-2, EN 61000-6-3
Compliance
This document is subject to change without notice