SYMPTOM
No LED display on
the front panel.
Alarm buzzer every
½ second when
AC supply is normal.
In the event of
power failure,
reduced backup
time.
Mains power normal
but led is flashing.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière – 44700 Orvault – FRANCE - www.infosec.fr
Hot Line : tel : + 33 (0)2 40 76 15 82 - fax : + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 02 06 04 206 12
POSSIBLE CAUSE
1. Battery missing
2. Faulty battery
3. Power switch was not
pressed for at least 5
seconds
1. UPS overload.
1. UPS overload or the
connected equipment is
defective.
2. Flat battery.
3. Battery defect due to the
high temperature of the
operating environment, or
improper operations.
1. Blown fuse.
2. Power cord is loose.
3. No mains power supply or
UPS is not on.
SOLUTIONS
1. Charge battery up to 8
hours
2. Replace with the same
type of battery.
3. Press and hold power
switch for at least 5 seconds.
1. Verify that the load
matches the UPS capacity.
Remove any non-critical load
e.g.: printer. Stop and restart
the UPS.
1. Remove any non-critical
load.
2. Recharge the battery 8
hours or more.
3. Replace with the same type
of battery.
1. Replace with the same type
of fuse
2. Reconnect the power cord
properly
3. Check the power supply