LERBAKKEN 10, 8410 RØNDE DENMARK.
Hazardous (Classified ) Location
Class I, Division 1, Group A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Installation notes
For installation in Class I the Transmitter must be installed in a suitable enclosure to meet installation
codes stipulated in The National Electrical Code (ANSI-NFPA 70).
Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the Entity
Concept. This concept permits interconnection of approved transmitters, meters and other devices in
combinations, which have not been specifically examined by FM, provided that the agency's criteria
are met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority
having jurisdiction over the installation.
The entity concept criteria are as follows: The intrinsically safe devices, other than barriers, must not
be a source of power. The maximum voltage Ui(V
Pi(Pmax), which the device can receive and remain intrinsically safe, must be equal to or greater than
the voltage (Uo or V
the barrier. The sum of the maximum unprotected capacitance (C
interconnecting wiring must be less than the capacitance (C
barrier. The sum of the maximum unprotected inductance (L
interconnecting wiring must be less than the inductance (L
barrier. The entity parameters Uo, V
the barrier manufacturer.
Revision date:
2014-09-16
24
FM Installation drawing 6335QF01
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
44
43
42
41
CH1
54
53
52
51
CH2
6335D2x
6336D2x
6337D2x
x = A :One channel
x = B :Two channel
or V
) and current (Io or I
OC
t
or V
and Io, I
OC
t
Version Revision
V6R0
WWW.PRELECTRONICS.COM
Non Hazardous Location
14
13
+
12
-
11
Barrier
250 < R < 1100 ohm
24
23
+
22
-
21
Barrier
Ex HART
Communicator
) and current Ii(I
), and maximum power
MAX
MAX
or I
) and the power Po which can be delivered by
SC
t
) for each intrinsically device and the
i
) which can be safely connected to the
a
) for each intrinsically device and the
i
) which can be safely connected to the
a
or I
, and C
and L
SC
t
a
6335V112-ES
R
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
R
for barriers are provided by
a
Page:
1/2

Publicidad

Tabla de contenido
loading

Tabla de contenido