LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of the single channel 6333A1A or the two channel 6333A1B the following must
be observed. The module shall only be Installed by qualified personnel who are familiar with the
national and international laws, directives and standards that apply to this area.
Marking
Class I, Division 2, Group A,B,C,D T4..T6
Class I Zone 2 Ex/AEx nA[ic] IIC T4..T6
Class I Zone 2 Ex/AEx nA IIC T4..T6
NIFW Class I Division 2, Group A,B,C,D
Terminal:
41,42,43,44
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000μF
Terminal:
51,52,53,54
Uo: 5 VDC
Io: 4 mA
Po: 20 mW
Lo: 900 mH
Co: 1000μF
Revision date:
2019-05-01
CSA Installation drawing 6333QC02
WWW.PRELECTRONICS.COM
T4: -40ºC to 85 ºC
T6: -40ºC to 60 ºC
44
+
43
13
-
42
11
41
CH1
54
+
53
23
-
52
21
51
CH2
Version Revision
V1R0
6333V105-ES
Hazardous Area
CL I, Div 2, GP ABCD
CL I, Zone 2, IIC
Terminal:
11-13
Functional Ratings:
U nominal ≤ 35 VDC;
I nominal ≤ 3.5 - 23 mA
Terminal:
21-23
Functional Ratings:
U nominal ≤ 35 VDC;
I nominal ≤ 3.5 - 23 mA
Page:
1/2
17