LED Driver
Installation Guide
EcoSystem
5-Series LED Driver
®
Driver Mounting
Remove lids before mounting. Avoid mounting driver close to heat source
such as light source.
Enclosure Mounting
Correct
Lid screws
Power Input and Digital Link Wiring
WARNING: Shock hazard. May result in serious injury or death.
Disconnect power before servicing or installing.
For proper wiring, follow wiring schematic on driver label. Torque range
on connector screws: 0.45 N•m to 0.50 N•m.
Solid or stranded
8 mm
copper wire
Ensure outer insulation extends across both rows of strain relief teeth.
Correct
Primary
N
N/C
N/C E1 E2
L
Lutron Technical Support Hotline +44.(0)20.7680.4481
Lutron, EcoSystem, and ) are registered trademarks of Lutron Electronics Co., Inc.
Incorrect
To secure mounting,
insert M3.5 screws here.
Wire Size
Digital Link
Length (max)
2.50 mm
500 m
2
1.50 mm
2
300 m
1.00 mm
200 m
2
0.75 mm
150 m
2
Incorrect
(insulation stripped too far)
(top view)
Mains Wire Size:
Digital Bus
Use 0.75 mm
– 2.50 mm
2
(side view)
Daisy Chain Wiring
EcoSystemR Daisy Chain Wiring
UNIT 1
Digital Bus
N/C E1 E2
Power Daisy Chain Wiring
UNIT 1
Primary
N
N/C
L
Load Wiring
SELV Secondary
N/C -V N/C +V
Secure Wiring
Replace the lids to clamp the wires
in place.
cable
2
Tighten the screws (0.5 N•m to
0.8 N•m) and tug gently on the wires
to ensure they are secure.
English
UNIT 2
Use 0.75 mm
Digital Bus
cable
N/C E1 E2
To EcoSystemR Digital Link
compatible devices.
UNIT 2
Primary
N
N/C
L
To additional EcoSystemR
LED Drivers. (Maximum units
to be daisy chained: 20)
Note:
For EcoSystemR daisy chain wiring, terminals can
accept two 0.75 – 1.50 mm
solid or stranded wires.
2
Note:
When placing multiple cables into the same strain relief,
all cable outside diameters must be the same.
Use 0.75 mm
– 1.50 mm
cable.
2
2
+V / Red
-V / Black
15 m Max Cable Length
Refer to spec submittal for 15 m cable
wire gauge requirements.
www.lutron.com/europe
P/N 041407b 01/2014
041407b
– 1.50 mm
2
2
LED
light
source