7. Select the correct wiring diagram. Loosen terminal screws. Insert conductors fully into proper terminals.
8. Tighten terminal screws as follows: SWITCH terminals: 12‑15 lb•in (1.4‑1.7 N•m); gROUND and NEUTRAL terminals 14.2 lb•in (1,6N•m).
9. Tighten the grounding buss mounting screw to 4.4‑8.9 lb•in (0.5‑1.0 N•m).
10. Take caution that there are no loose wire strands.
11. Reinstall cover. The handle must be in the "OFF" position. Start each of the four screws by hand to avoid cross threading.
Tighten the four cover screws to 24 lb•in (2.7 N•m). Make sure the sealing O‑rings are in place under the screw heads.
12. An additional DANgER label (D64558) has been supplied loose with this product as a convenience. Apply label to the
outside of the front cover (see figure M‑11) if the product application does not pose the risk of the label being removed
through cleaning, hose down or any other means.
13. Consult factory for auxiliary contact availability.
14. For all catalog suffix ending in –J or –H refer to selector switch instruction below. See torque setting below.
http://literature.rockwellautomation.com/idc/groups/literature/documents/td/800‑td008_‑en‑p.pdf
http://literature.rockwellautomation.com/idc/groups/literature/documents/td/800‑td009_‑en‑p.pdf
800H selector switch terminal screw torque 6‑8 lb‑in (0.7‑0.9 N‑m) of torque. Wire gauge #18‑10awg.
800FP‑SL32 selector switch terminal screw torque 6‑8 lb‑in (0.7‑0.9 N‑m) of torque. Wire gauge #18‑12awg.
Fig. M-3
6
Fig. M-5
1
13
Fig. M-9
Power
in
B
19

WIRING DIAGRAMS

125 VAC, 1Ø
240 VAC, 1Ø
NOTE : "G" designates ground wire and yellow and green grounding buss.
PD2520
05/17
(PAGE 2)
7
8
5
11
9
Fig. M-6
14
5
15
Power
out
C
A
240 VAC, 3Ø
240 VAC, 1Ø
480 VAC, 3Ø
480 VAC, 1Ø
600 VAC, 3Ø
600 VAC, 1Ø
Fig. M-4
10
12
Fig. M-7
16
18
Fig. M-10
120/208 VAC, 3ØY
240/480 VAC, 3ØY
125/240 VAC, 1Ø
347/600 VAC, 3ØY
1 Drill spots. Drill in locations for user installed back
feed conduit entrance. NOTE: Back feed is not
permitted in Type 12 applications. A Listed/Certified
closure plug rated Type 4X, 12 must be installed
when not using existing conduit entrance hole.
2 Enclosure
3 Mounting foot (4)
4 Drill spots both ends
5 Form condensate drip loops as shown.
6 Terminal screws
7 Grounding buss
8 Ground buss mounting screw
9 User installed thru-feed conduit entrance
10 Switch
11 Neutral buss
12 Breather drain (not included)
13 User installed conduit entrance for dual top feed or
bottom feed
14 Back feed conduit. See drill spots Fig. M-1.
15 Switch release tab. Pull to remove switch.
16 Listed/Certified conduit hub rated Type 4X, 12 (One
supplied)
17 LINKOSITY Power out
18 Align rib with slot.
1
15
D
B
NOTICE: This manual motor con-
troller carries a maximum rating of:
30 A
1 HP
3 HP
5 HP
7.5 HP
15 HP
15 HP
Fig. M-8
17
Fig. M-11
600 VAC
120 VAC 1Ø
200-240 VAC 1Ø
480 VAC 1Ø
200-240 VAC 3Ø
480 VAC 3Ø
600 VAC 3Ø