Installation instructions
Piping Joints Thermal Insulation:
Wrap the piping joints with thermal
insulation materials and then wrap
with a vinyl tape.
Piping Thermal Insulation:
a. Place the drain hose under the piping.
b. Insulation material uses polythene foam over 6mm in thickness.
Note: Drain hose is prepared by user.
Drain pipe should point downward for easy drain flow.
Do not arrange the drain pipe twisted, sticking out or wave
around, do not immerse the end of it in water.
If an extension drain hose is connected to the drain pipe, make
sure to thermal insulated when passing along the indoor unit.
When the piping is directed to the right, piping, power
Cord and drain pipe should be thermal insulated and
fixed onto the back of the unit with a piping fixer.
Base
A. Insert the pipe fixer to the slot.
Piping Connection:
a.Before unscrewing the big and the small sealing caps, press the small
sealing cap with the finger until the exhaust noise stops, and then loosen
the finger.
b. Connect indoor unit pipes with two wrenches. Pay special attention
to the allowed torque as shown below to prevent the pipes, connectors
and flare nuts from being deformed and damaged.
c. Pre-tighten them with fingers at first, then use the wrenches.
If you don't hear the exhaust noise, please contact with the merchant.
Model
Liquid Side (
5,7,8,9,10,12,14,15,18,24K
Liquid Side (
18K ,22,24K ,28,30,36K
#
#
Gas Side (
5,7,8,9,10K
Gas Side (
12,14,15,18K
Gas Side (
18K ,22,24,28,30,36K
#
Gas Side (
36K
#
Note: The unit of 18K
,24K
#
Thermal insulation
Piping fixer
Base
B. Press to hook the pipe fixer onto the base.
Pipe size
φ6mm or
1/4 inch)
φ9.53mm or
3/8 inch)
φ9.53mm or
3/8 inch)
φ12mm or 1/2
inch)
φ16mm or
5/8 inch)
φ19mm or
3/4 inch)
,36K
is bigger than the unit of 18K,24K,36K.
#
#
Power cord
Power cord 1
(for heat-pump)
Defrost cable(for heat-pump)
Insert here
large
pipe
drain
small
hose
pipe
Piping fixer
Torque Nut width Min.thickness
17mm
15~20N·m
22mm
30~35N·m
22mm
30~35N·m
50~55N·m
24mm
27mm
60~65N·m
32mm
70~75N·m
8
wrapped with vinyl type
Large pipe
Thermal insulation
tube
Drain hose
(prepared by user)
large
pipe
drain
small
hose
pipe
Hook here
Base
0.5mm
0.6mm
0.6mm
0.6mm
0.6mm
1.0mm
Small
pipe