OPTION: WIRE CONNECTION
[OPCION: CONEXION DE CABLE ]
(OPTION: CONNEXION DE CÂBLE)
1
Cu / Al 60° / 75° C
14 – 10 AWG – 35 lb. in. (35 lb-po) [4.0 N-m]
8 AWG – 40 lb. in. (40 lb-po) [4.5 N-m]
15 - 30
Amp
Cu / Al 60° / 75° C
8 AWG – 40 lb. in. (40 lb-po) [4.5 N-m]
6 – 4 AWG – 45 lb. in. (45 lb-po) [5.1 N-m]
3 – 2/0 AWG – 55 lb. in. (55 lb-po) [6.2 N-m]
35 - 125
Amp
Required Conductor Stranding [ Cantidad de hebras requeridas en alambre ] (Âmes de
conducteur requises)
Conductor Size
[ Tamaño de alambre ]
(Taille du conducteur)
AWG or kcmil [ mm
]
2
AWG ou kcmil [ mm
2
]
14 – 2 [ 2.1 – 33.6 ]
1 – 2/0 [ 42.4 – 67.4 ]
* Not to be used with Aluminum 14 AWG (2.1 mm
calibre 14 AWG ] (Ne pas utiliser avec câble en aluminium 14 AWG (2,1 mm
OPTION: NUT KEEPER KIT
[ OPCION: PLACAS TERMINALES PARA FIJACION DE CONEXIONES ]
(OPTION : ENSEMBLE DE PLAQUE-ÉCROU)
Technical Support:
Soporte Técnico:
Services de soutien technique :
Subject to change without prior notice [Sujeto a cambio sin previo aviso] (Sous réserve de modifications sans préavis)
Siemens Industry, Inc. , Norcross, GA 30092 U.S.A.
clic
2
Number of strands [ Cantidad de hebras ] (Nombre de brins)
Cu
Class [ Clase ]
Class [ Clase ]
(Classe) B
(Classe) C
7
19
19
37
2
) conductors [ No utilizar alambre de aluminio
Toll Free [Lada gratiuita] (Sans Frais): 1-800-241-4453
4
3
ARCING POTENTIAL. Terminal shields required for
347V or 600V applications.
RIESGO DE ARQUEO. Cubiertas de terminal requeridas
para aplicaciones de 347V o 600V.
RISQUE D' ARC. Blindages terminaux requis pour 347V
ou 600V applications.
Al
Class [ Clase ]
(Classe) B
7 *
19
2
))
TNKG3
4 / 4
TYPE HGGA/LGGA
5
ON / I Side [Lado] (Côté)
TYPE HGGA/LGGA
6
OFF / O Side [Lado] (Côté)
TYPE HGGA / LGGA
DANGER [PELIGRO]
Internet: www.usa.siemens.com/powerdistribution
A
B
7
© Siemens Industry Inc. 2013
806933 A06