120 VOLT MOTOR KIT
Green
Black
White
15A 120V
Motor
Recp.
A
The orange wire is not used. Double it over and cover the bare end with
electrical tape.
B
The red wire is not used on single speed motors. Double it over and cover
the bare end with electrical tape or wirenut.
240 VOLT MOTOR KIT
Black
Green
Orange
Orange
15A 230V
Red
Black
Orange
Green
White
Motor
Recp.
INSTALLATION
1. Install the motor in the mounting cradle as shown.
2. Remove the junction box from the cooler.
3. Remove 120 volt pump and pump receptacle furnished with cooler and
replace it with the 240 volt LSP-94 pump and pump receptacle. (see
replacement parts list)
4. Wire the pump and motor receptacles per the schematic shown above.
5. Place both receptacles in the junction box as shown and re-attach the
junction box to the cooler top.
Green
Black
Orange
15A 230V
Motor
Recp.
A
The white wire is not used. Double it over and cover the bare end with
electrical tape or wirenut.
B
The red wire is not used on single speed motors. Double it over and cover
the bare end with electrical tape.
Black
Green
White
Pump
Red
Lo
Black
Hi
White
Red
Com
Black
Green
White
Green
GND
Orange A
Pump
B
Red
Lo
Black
Hi
Orange
Com
Green
GND
A
Black
Green
Orange
Pump
Red
Lo
Black
Hi
Orange
Red
Com
Black
Green
Orange
Green
GND
White A
OPERATION
Power
Supply
BLOWER BELT ADJUSTMENT
Correct belt tension adjustment is important. Incorrect adjustment increases
power consumption and shortens belt and motor life.
Install belt over motor and blower pulleys.
(A) check belt tension by squeezing (deflecting) belt. Proper tension will allow
deflection of 1/2 to 3/4 inch.
(B) To increase or decrease belt tension, loosen bolt in slot of motor support
brcket. Adjust belt to desired tension and re-tighten bolt.
PRE-WET PADS
For maximum cooling efficiency, prior to the initial start up of the cooler
remove the pad frame assemblies from the cooler and spray the pad and
frames thoroughly with water from a garden hose.
Put the pad frame assemblies back on the cooler and while the pads are still
Power
wet start the cooler with the pump on.
Supply
BUILT-IN WINTER CLOSURE
An exclusive feature of your cooler (models in the 4800 to 6800 CFM range)
which is provided is the full closure damper. Your cooler is shipped from the
factory with the damper temporarily fastened to the side of the blower with a
shipping screw. Remove the screw and store the damper for later use during
winter months.
1. For Winter use of a damper, slide damper into cooler below the blower.age.
2. When starting the cooler in the Spring, remove the damper and store in a
safe place.
Power
Supply
(Down discharge units only)
Page 3