TROUBLESHOOTING GUIDE:
Should an obvious problem occur with your cooler consult the following table. If you
cannot correct the problem, or if it persists, contact qualified service personnel.
PROBLEM / SYMPTOM
POSSIBLE CAUSE
Float valve out of adjustment
Water draining from unit
Float movement obstructed
Float valve non-functional
Dry pads
Pump intake clogged
Water pump non-functional
Clogged water line
Pad trough clogged
Switch non-functional
Wiring non-functional
Water turned off to cooler
Electrical power disconnected
Motor does not start or no air delivery
Non-functional motor
Non-functional switch
Inadequate air delivery
Insufficient air exhaust
Pads plugged
Motor cycles on & off
Low voltage
Non-functional motor
Pad frame(s) or air outlet grille removed
Blower rubbing on housing
Noisy operation
Blower wheel set screws loose
Inadequate exhaust
Excessive humidity in house
WIRING DIAGRAM
6 Frigiking Evaporative Window Cooler - Use and Care Manual