COZY W255GPPR Instrucciones De Instalación Y Funcionamiento página 22

Ocultar thumbs Ver también para W255GPPR:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

STEP 6.
Slide the Pilot Pro cover (31) over the
controls. Secure in place with:
-
x2 Screw with knob (33)
NOTE:
Hand-tighten only.
Do not over tighten.
STEP 7.
Failure to follow the steps outlined below for each appliance connected to the venting system
being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into
operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code, CSA B149.1 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3. As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they are operating at maximum speed. Do not operate
a summer exhaust fan.
STARTING PILOT PRO SYSTEM PER ANSI Z21.71
!
WARNING: CARBON MONOXIDE POISONING HAZARD
6. Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or Natural Gas and Propane
Installation Code, CSA B149.1.
9. After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-
fired burning appliance to their previous conditions of
use.
Page 22
33
31
33
1018454-E

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

W255gppdW355gpprW355gppdW505gpprW505gppd

Tabla de contenido