When batteries are installed in racks, the following recommendations must be obeyed:
 Each cell should be supported separately by the rack over its full length. Never stack a battery on another.
 Make sure that the battery racks are stable, horizontal and firmly anchored on the floor
 Precautions must be taken if batteries are being installed in metallic cabinets or on racks. Keep an air safety distance of at
least 0.5 inch between insulated cables and electrically conductive parts, or use additional insulation
 The use of metal clamps on the cells is not recommended. A system made of insulating material should be used
Model
Part number
Nominal voltage
Nominal capacity (C20)
Reserve capacity*
Number of cells per battery
Maximum charge current:
Approximate weight:
Terminal: threaded insert stud
CCA to DIN
CCA to SAE
General
Operating temperature
Nominal operating temperature:
Storage temperature
Compliancy:
* Reserve capacity = time a battery can be loaded with 25 Amps at 80ºF (26,7ºC) until the battery voltage is 10.5V
Rated capacity @77ºF / 25ºC
Model
AGM-SL 12/150Ah
AGM-SL 12/200Ah
Battery model
AGM-SL 12/150Ah
AGM-SL 12/200Ah
Final discharge voltage
Tensión final de descarga
USE OF BATTERY RACKS
Order number battery interconnector AGM-SL series:
Nº de pedido de battery interconnector AGM-SL series:
GENERAL SPECIFICATIONS AGM-SL SERIES
AGM-SL 150Ah
63001500
12V
150 Ah
250 min
6
43 Amps
97 Lbs / 43.8 kg
M6
490 A
790 A
–4 to 131ºF / –20 to 55ºC
41 to 95ºF / 5 to 35ºC, recommended at 77ºF / 25ºC
–13°F to 185°F / –25°C to 85°C
EU Directive 2006/66/EC
C20
C10
150Ah
143Ah
129.5Ah
200Ah
191Ah
163Ah
FINAL DISCHARGE VOLTAGE
< 28 Amps
< 35 Amps
10.8 Volts
AGM-SL 200Ah
63001851
12V
200 Ah
420 min
6
53 Amps
113 Lbs / 51.2 kg
M6
580 A
930 A
RATED CAPACITY
C5
C3
C1
118.2Ah
94.3Ah
158Ah
126Ah
Discharge current / Corriente de descarga
28 – 71 Amps
35 – 88 Amps
10.5 Volts
Capacity affected
by temperature:
32ºF (0ºC)
68ºF (20ºC)
77ºF (25ºC)
104ºF (40ºC)
28 – 143 Amps
> 143 Amps
35 – 177 Amps
> 177 Amps
10.2 Volts
67909198
86%
97%
100%
103%
9.6 Volts

Publicidad