General Specifications - Southwire 41151S Instrucciones De Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Input Limits
Function
Maximum Input
Voltage AC or DC

General Specifications

Insulation
Class 2, Double insulation.
Display
LED
Operating Temperature
32°F to 104°F (0°C to 40°C)
Storage Temperature
5°F to 131°F (-15°C to 55°C)
Relative Humidity
Maximum, non-condensing: 85%
Operating Altitude
0-2000 meters
Weight
0.2 pounds (90.7grams)
Dimensions:
5.5" x 1.7" x 1.1" (140mm x 43mm x 28)
Safety:
UL: 61010 - 1:2012, 61010-2-030: 2012,
61010-2-033: 2014
EMC:EN61326-1:2013, EN61326-2-2:2013
Ingress Protection
IP42
3
International Safety Symbols
Potential danger. Indicates the user must refer to the manual for important
safety information.
Indicates hazardous voltages may be present
Equipment is protected by double or reinforced insulation.
MAX
Indicates the terminal(s) so marked must not be connected to a circuit where the
600V
voltage with respect to earth ground exceeds the maximum safety rating of the
meter.
Indicates the terminal(s) so marked may be subjected to hazardous voltages.
Safety Category Ratings
Category
Brief Description
Typical Applications
Rating
Single phase receptacles
CAT II
and connected loads
Three phase circuits
CAT III
switchgear and distribution panels
and single phase
lighting circuits in
commercial buildings
The measurement category (CAT) rating and voltage rating is determined by a
combination of the tester and the test probes. The combination rating is the
LOWEST rating of any individual component.
AWARNING:
from one or both test probes. Refer to Input Limits section of this manual for maximum
voltage ratings.
III
III
soruce
4

Publicidad

Tabla de contenido
loading

Tabla de contenido