Riello MG569 Manual De Instrucciones página 20

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
RE-CYCLE FUNCTION
The control box allows re-cycling, i.e. the complete repetition of the starting programme, for 3 attempts
maximum, in the event the flame goes out during
POST-VENTILATION FUNCTION
Post-ventilation is a function that maintains air ventilation even after the burner is switched off. The
burner switches off when the limit thermostat (TL) opens, cutting off the fuel supply to the valves.
To use this function the reset button must be pressed when the limit thermostat is not switched over
(BURNER SWITCHED OFF).
Post-ventilation time can be set to a maximum of 6 minutes. Proceed as follows:
®
Press and hold the reset button for at least 5 seconds till the LED indicator changes to red.
®
Set the desired time pressing the button repeatedly: once = post-ventilation for 1 minute.
®
After 5 seconds the control box automatically shows the minutes set by the red LED flashing:
1 pulse = post-ventilation for 1 minute.
To reset this function, press and hold the button for at least 5 seconds at least, till the LED indicator
changes to red then release it without carrying out any operation, then wait for 20 seconds for the
burner to start.
If during post-ventilation there is a new request for heat, post-ventilation time is halted and a new
operating cycle starts when the limit thermostat (TL) switches over.
The control box leaves the factory with the following setting: 0 minutes = no post-ventilation.
CONTROL BOX RESET
To carry out the control box reset, proceed as follows:
®
Press the reset button for at least 1 second.
In the event of the burner not restarting it is necessary to check if the limit thermostat (TL) is
closed.
3008
operation.
5
GB

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

30029493002967

Tabla de contenido