9. NEW LCD SETTINGS
1. I / P Voltage Range Setting
Default : Input Voltage : LO = 170V, HI = 270V.
LO : 120V ~ 200V (One Touch: +/- 1V)
HI : 250V ~ 280V (One Touch: +/- 1V)
Mark : 1. Return point= +/- 10V from the transfer point.
2. Press Enter to enable the setting. No need to re-start the inverter.
2. O/P Voltage /Frequency Setting
Default: 220VAC , 50HZ
Voltage: 220VAC / 230VAC / 240VAC Seleccionable
Frequency: AC= Synchronized to AC., DC= 50HZ / 60HZ Seleccionable
Mark : Press Enter to confirm.
Need to re-start the inverter to Enable the setting.
3. AC/DC Prior Setting (Optional) Functioning only under AC Mode.
Default: AC TO AC
Select "AC TO AC" (AC MODE) for AC Prior, "DC TO AC" (INVERTER MODE) for DC
Prior.
Mark:1. When the inverter is set to "DC Prior", if the inverter itself diagnoses problems,
it will auto change to AC if AC normal.
2. Press Enter to confirm.
Need to re-start the inverter to Enable the setting.
4.Green Power On/Off Setting (Optional) Functioning only under INVERTER Mode.
Default: Off.
Green Power Off: System running continuously.
Green Power On: System Auto Shutdown when Load < Pre-setting
Mark : Press Enter to enable the setting. No need to re-start the inverter.
5.Green Power Load & Time Setting (Optional)
Default: Time period for next detecting: 30 Sec.
Time: 15 Sec., 30 Sec., 45 Sec. 60 Sec selectable.
Mark:1. Detecting load: 5~10VA
2. When the load is less than 5~10VA,the inverter will auto turn off
and count the pre-set time (30 Sec.),then, re-start.
3. Press Enter to enable the setting. No need to re-start the inverter.
26
6.Battery Shutdown Voltage & Current Setting (48V / 24V)
Default: MIDDLE
HIGH: 42V (21V) / MIDDLE: 40V (20V) / LOW :38V (19V) Selectable
Mark:1. Low Voltage warning point: 42.5 V (21.5V)
2. Press Enter to enable the setting. No need to re-start the inverter.
7.Battery Charging Current Setting
Default: Middle
LOW (100AH) - MIDDLE (300AH) - HIGH (600AH)
Mark : Press Enter to enable the setting. No need to re-start the inverter.
NOTE : 1.2KVA ONLY 24VDC