UCT-1, 2 & 3 Instructions
and Maintenance
Important: Read before installing and
retain for future reference.
Lamp Code:
General: Read all warnings and information on carton(s) and product(s). This trim kit is suitable for damp locations in ambient
temperatures of 25 degrees C maximum and is to be used only with those luminaires listed above. These instructions do not
attempt to cover all installation and maintenance situations. If additional information is required, contact your nearest Hubbell
representative for assistance.
Warning: Improperly installed fixtures can cause injury, shock, electrocution and fire hazards. Install and maintain with quali-
fied personnel to meet all applicable Codes and Ordinances. Turn power OFF prior to installation or performing any mainte-
nance. Ground properly and use appropriate wire connectors. Input voltage must be matched to the appropriate ballast leads.
Follow lamp and other equipment manufactures' instructions. Installing electricians are responsible for evaluating local condi-
tions and ensuring safe operation. Never remove the 1/4-20 bolts to un-install.
General Installation Information
1. Recommended tools: screw driver, 3/8" socket and ratchet.
2. Use 90 degrees C minimum supply wire and utilize the units' cable clamp to keep the wires away from the ballast.
3. Ensure existing housing does not leak from above and is secured properly to the canopy and can safely support the
additional weight of the retro-fit assembly. If not, seal and reinforce attachment system.
Installation
Note: Turn power OFF prior to any work.
1. Open, remove and discard lens frame assembly from existing fixture.
2. Remove lamp, reflector, socket, ballast cover and hardware on door flange.
3. Remove any caulking from the corners where the hinges will be. Orient and hang trim
panel (fig. 1) on housing's flanges with existing ballast on the left or right side. Ensure
panel is against rear flange with the hardware facing you.
4. Place Ballast Housing's mounting bolts through panel's keyholes (fig. 2) with the lid
latch end up. Ensure bolts are secured in the keyhole slots .
5. Remove lid and discard. For units without ballast, wire existing ballast to the new
socket. For units with ballast, disconnect existing ballast and run supply wires (you
may have to add to the length) to matching voltage leads of the new ballast (cap off
unused leads). In both cases, connect unit's ground wire to existing ground wires.
Secure wires with the unit's cable clamp.
6. Hinge panel up and to the rear until the safety latch engages. Slide locking screw to
the rear, raise panel against flange, slide the locking screw forward until the safety tab
falls into the slot (fig. 3) and tighten the screw.
7. Slide the Mounting Bolts out of the keyhole slots to the rear until the locator cones
(above the two bolts) seat into the keyhole's large holes (fig. 4).
8. Position and orient Lens Assembly with a non- hinge/latch side facing the direction
where there may be a glare problem (reflectors can be adjusted downwards). Place
the lead-in cone (fig. 5) through the panel's 4" hole and rotate assembly so the two
bolt heads slide into the key holes. Rotate unit clockwise until it locks and reposition
the assembly to the rear if the Ballast Housing has rotated during installation. Ensure
the unit is secured . Push latch up and lower lens. Fine tune alignment if necessary
and tighten bolts with a 3/8" socket. Ensure bolts are tight. Install lamp tightly and
close lens door.
Glare Control: See UCL Instructions and Maintenance sheet: "Optional"
Maintenance
See UCL Instructions and Maintenance sheet for Lamp Replacement and Optical As-
sembly Replacement or Un-Install.
Hubbell Lighting, Inc., A Subsidiary of Hubbell Inc.
2000 Electric Way, Christiansburg, VA 24073-2500
Tel: 540-382-6111
UCT-1, 2 or 3 for use with Hubbell UCL or UCB series ballast housings and
UCO optical assemblies in the following Products rated minimum 400 watts,
minimum size 21-1/8" square, 7-1/2" deep. UCT-1: Whiteway TD/RA-II/VN,
Cooper CLS; UCT-2: LSI MA/DA, Whiteway RA, Jet-Phillips Houstonian
(old style); UCT-3: Jet-Phillips SHO/RHO, Guardian MC-1411 fixtures.
Date:
FAX: 540-382-1526
268-1190-9901
Printed in U.S.A.