INSTALLATION AND MAINTENANCE INSTRUCTIONS
102 mm
B501AP
59 mm
DESCRIPTION
The NFXI-VIEW is an addressable plug-in type smoke detector suitable
for extremely high sensitivity applications. These sensors are designed for
open area protection and must only be connected to control panels (CIE)
that use a compatible proprietary communication protocol for monitoring
and control. The CIE can communicate with a device using either the
200/500 Series Protocol (CLIP) or Advanced Protocol (AP).
Each device can have its own unique address, which is set using two rotary
code switches on the underside of the product. Two red/green/yellow LEDs
on each sensor provide a local 360
controlled by CIE). Remote LED indicator capability is available as an
optional accessory wired into the standard base terminals.
The output from the detector requires a sophisticated algorithm in the CIE,
including drift compensation, to process the signal.
This smoke sensor contains an isolator. When installing the device using
the isolator, check the panel documentation for details of how many
isolators can be used on a loop
The NFXI-VIEW is designed to be backward compatible with the FSL-751E.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Max. Standby Current:
250 μA @24 V & 25
(Red LED blink enabled): 300 μA @24 V & 25
Max. Alarm Current:
add 3 mA @ 24 V & 25
Operating Humidity Range: 10% to 93% Relative Humidity (non condensing)
Power Up Time (max):
3s
Isolator Characteristics
Operating voltage:
≤ 32V
Maximum rated continuous current with the isolator closed (I
Maximum rated isolator current (under short circuit) (I
Max. leakage current (I
max) with the isolator open (isolated state): 12mA
L
Max. series impedance with the isolator closed (Z
This device is tested and certified to EN54-7 and EN54-17.
Avoid locating the sensor in direct sunlight
WIRING
Refer to the installation instructions supplied with the plug-in sensor base
for wiring details.
Note: All wiring must conform to applicable local and national codes and
regulations.
Disconnect loop power before installing sensors
SENSOR INSTALLATION
1. Set the sensor address (see Figure 1) by turning the two rotary switches
on the underside of the sensor (using a screwdriver to rotate the
wheels), selecting a number between 01 and 159. (Note: The number
of addresses available will be dependent on panel capability, check the
panel documentation for information). Record the address on the label
attached to the base.
2. Insert the sensor into the base and rotate clockwise until it locks into place.
3. After all the sensors have been installed, apply power to the system.
4. Test the sensors as described under TESTING.
N200-400-00
Notifier by Honeywell, 140 Waterside Road, Hamilton Industrial Park, Leicester, LE5 1TN, UK
HIGH SENSITIVITY SMOKE SENSOR
23 mm
110 g
visible sensor indication (LEDs are
o
C (no comm.)
o
C (comm. every 5s)
o
C (2x red LED on)
o
max): 1A
s
max): 160 m ohm at 15Vdc.
c
Caution
WARNING
NFXI-VIEW
55°C
-10°C
Anti-Tamper Features
These sensors includes a feature that, when activated, prevents removal of
the sensor from the base without the use of a tool. Refer to the installation
instructions for the sensor base for details of how to use this feature.
Dust covers help to protect units during shipping and when first
installed. They are not intended to provide complete protection
against contamination, therefore sensors should be removed before
construction, major re-decoration or other dust producing work is
started. Dust covers must be removed before a system can become
operational.
MAINTENANCE
Before cleaning, disable the system to prevent unwanted alarms:
1. Remove the sensor to be cleaned from its base.
2. Gently release each of the four cover tabs that hold the cover in place
(see Figure 2) and remove the sensor cover.
max): 1A
c
3. Vacuum the outside of the screen carefully without removing it.
4. Remove the screen and air guide assembly by pulling it straight out.
5. Use a vacuum cleaner to remove dust and debris from the sensing
chamber, air guide and inside of the screen.
6. Re-install the assembly by aligning the arrows on the plastic that
indicate the positioning and gently press it home.
7. Re-install the sensor cover. Use the cover tabs and LEDs to align the
cover with the sensor and snap the cover into place.
8. When all sensors have been cleaned, restore power to the loop and
test the sensors as described under TESTING.
Figure 1: Rotary Address Switches
X 10
X 1
CAUTION
Figure 2: Cleaning the Sensor
SENSOR COVER
COVER REMOVAL TABS
SCREEN
AIR GUIDE
OPTICAL SENSING
CHAMBER
E N G L I S H
I 56- 6296- 000
I56-6296-000

Publicidad

loading

Resumen de contenidos para Honeywell NOTIFIER NFXI-VIEW

  • Página 1 2. Insert the sensor into the base and rotate clockwise until it locks into place. 3. After all the sensors have been installed, apply power to the system. 4. Test the sensors as described under TESTING. N200-400-00 Notifier by Honeywell, 140 Waterside Road, Hamilton Industrial Park, Leicester, LE5 1TN, UK I56-6296-000...
  • Página 2 Smoke sensors cannot last forever, and we recommend replacement after 10 years. 0832 19 DOP-IFD201 Notifier Fire Systems by Honeywell Pittway Tecnologica S.r.l. Via Caboto 19/3 34147 TRIESTE, Italy EN54-7: 2000 / A1: 2002 / A2: 2006 Smoke detectors EN54-17: 2005 Short Circuit Isolators...
  • Página 3 LED para alinear la cubierta con el sensor y ajústela en su posición. central; compruebe la documentación para obtener más información). N200-400-00 I56-6296-000 Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana...
  • Página 4 Los sensores de humo tienen una duración limitada y se recomienda su sustitución cada 10 años. 0832 19 DOP-IFD201 Notifier Fire Systems by Honeywell Pittway Tecnologica S.r.l. Via Caboto 19/3 34147 TRIESTE, Italy EN54-7: 2000 / A1: 2002 / A2: 2006 Detectores de humo...
  • Página 5 NFXI-VIEW D E U T S C H HOCHEMPFINDLICHER RAUCHMELDER INSTALLATIONS- UND WARTUNGSANLEITUNG Abbildung 1: Adress-Drehschalter 102 mm 55°C 23 mm B501AP 59 mm -10°C 110 g X 10 BESCHREIBUNG Schalten Sie die Stromversorgung ein, nachdem alle Melderen installiert sind. Der NFXI-VIEW ist ein addressierbarer, steckbarer Rauchmelder für äußerst hochempfindliche Anwendungen.
  • Página 6 Brandmeldern die Umgebungsbedingungen beachten. Rauchmelder halten nicht ewig. Wir empfehlen einen Austausch nach 10 Jahren. 0832 19 DOP-IFD201 Notifier Fire Systems by Honeywell Pittway Tecnologica S.r.l. Via Caboto 19/3 34147 TRIESTE, Italy EN54-7: 2000 / A1: 2002 / A2: 2006 Rauchmelders...
  • Página 7 Inscrire l’adresse sur l’étiquette collée sur la socle. le détecteur en se servant des languettes du couvercle et des DEL. Emboîter le couvercle à sa place. N200-400-00 Honeywell Life Safety SA, Liege Airport Business Park B50, 4460 Grâce-Hollogne - België I56-6296-000...
  • Página 8 Les détecteurs de fumée n’ont pas une longévité illimitée et nous recommandons de les remplacer tous les dix ans. 0832 19 DOP-IFD201 Notifier Fire Systems by Honeywell Pittway Tecnologica S.r.l. Via Caboto 19/3 34147 TRIESTE, Italy EN54-7: 2000 / A1: 2002 / A2: 2006 Détecteurs de fume...