10.3
Modbus TCP
02.07.2019
BlueNet PDU BN3000/3500/5000/7000/7500 y BlueNet Power Unit 2
n
blueNet2VariableUpperWarningTrap
–
(1) Master/Inlet/Phase 1 (Phase) "Phase 1": Voltage has
reached a warning high state: 218.5 V (Threshold: 200.0 V)
–
(2) Master/Combination Sensor S2 (I2C Temperature-
Humidity Sensor) "Combination Sensor S2": Humidity has
reached a warning high state: 47.6 % (Threshold: 40.0 %)
n
blueNet2VariableUpperAlarmTrap
–
(1) Master/Inlet/Phase 1 (Phase) "Phase 1": Voltage has
reached a critical high state: 219.7 V (Threshold: 100.0 V)
–
(2) Master/Combination Sensor S2 (I2C Temperature-
Humidity Sensor) "Combination Sensor S2": Humidity has
reached a critical high state: 47.6 % (Threshold: 40.0 %)
n
blueNet2SensorStatusAlarmTrap
–
(1) Master/Temperature Sensor S2 (I2C Temperature
Sensor) "Temperature Sensor S2" is Lost
–
(2) Master/Inlet/Phase/Fuse 1 (16A;C) "Fuse 1" is Off
n
blueNet2SensorStatusOkTrap
–
(1) Master/Temperature Sensor S2 (I2C Temperature
Sensor) "Temperature Sensor S2" is On
–
(2) Master/Inlet/Phase/Fuse 2 (16A;C) "Fuse 2" is On
n
blueNet2PduStatusAlarmTrap
–
Slave-1 (Slave) "Slave-1" is Lost
n
blueNet2PduStatusOkTrap
–
Slave-1 (Slave) "Slave-1" is On
n
blueNet2RCMSelftestResultTrap
–
Maestro: RCM Self-Test finished, 1 out of 1 succeeded
n
blueNet2ReconfigAgentNotification
blueNet2ShutdownAgentNotification
n
n
coldStart
La función "Modbus TCP" se puede activar o
desactivar según sea necesario. Esta función está
desactivada por defecto.
Se admiten varios protocolos Modbus TCP. Las descripciones de
los protocolos se pueden descargar de la página web de Bach-
mann.
Modbus TCP V2.00
n
Antes de leer los valores de una PDU se debe definir correcta-
mente el ID de la PDU, la entrada (PDU) o la salida (PU).
n
No es necesario para una configuración maestra pura sin PDU
esclava.
n
Código de función 0x03 (Read Holding Registers) para leer los
valores medidos.
Otras cuestiones
Modbus TCP
133