4.3
Slide switch
By means of the slide switch, an adjustable selection of relays (see channel MM,
page 13) can be switched on (I) or off (0) manually. When the slide switch is set
to Auto, the adjustments of the channels M1 ... M5 are valid.
Manually OFF
= 0 (left)
Manually On
= I (right)
Automatic mode = Auto (mid position) – adjustments made in M1 ... M5
0 Auto I
Slide switch
4.4
Flashing codes and warning symbols
4.4.1 LED flashing codes
green:
everything OK
green flashing: manual mode
red flashing:
S-Bus cable broken or controller not detected
4.4.2 Warning symbols
⚠ = no S-Bus communication
☛ = manual mode (see chap. 5.3):
flashing:
slide switch in position I
permanent: slide switch in position 0
28
5
Menu system
5.1
Channel overview
Channel
Description
S1
D Value at sensor 1
S2
D Value at sensor 2
S3
D Value at sensor 3
S4
D Value at sensor 4
S5
D Value at sensor 5
S6
D Value at sensor 6
R1
D Speed relay 1
R2
D Speed relay 2
R3
D Speed relay 3
R4
D Speed relay 4
R5
D Status relay 5*
VC
D Version compatibility
EC
D Error code
M1
P
Manual mode R1
M2
P
Manual mode R2
M3
P
Manual mode R3
M4
P
Manual mode R4
M5
P
Manual mode R5
MM
P
Slide switch manual mode
T1
P
Sensor type sensor 1
T2
P
Sensor type sensor 2
T3
P
Sensor type sensor 3
T4
P
Sensor type sensor 4
T5
P
Sensor type sensor 5
T6
P
Sensor type sensor 6
SA
P
Sub-address
PG
D Program
VN
D Version number
* R5 is a potential-free relay not suitable for speed control. Therefore, its status is
indicated with 0 % or 100 % respectively.