5.
A01 Thermostat Setting
In case of Probe NTC100K, the procedure allows to adapt the A01 value to the installation conditions.
Set the Controller in OFF (L4 ON) through the button P2
To enter in Setting Procedure push the button P1 for about 10 seconds
The Controller goes in A01 Thermostat Setting: the Led L2 is blinking
Through the buttons P2 and P1 increase/decrease the value of the thermostat with step of 5°C
The thermostat value is signalled as following:
Led L1 blinking:
Led L2 blinking:
Led L3 blinking:
Led L4 blinking:
To Memorize and Exit push contemporarily the buttons P1 and P2
6.
U1 / U9 Speed directly Setting
This procedure allows to adapt the speed's regulations to the used fan and the installation conditions
Set the Controller in OFF (L4 ON) through the button P2
To enter in Setting Procedure push contemporarily the buttons P1 and P2 for about 10 seconds
The Controller goes in U1 Minimum Speed Setting: the Led L3 is blinking and L1=ON.
In this condition the Controller manages the fan at the U1 Speed
Through the buttons P2 and P1 increase/decrease the fan speed
The Max Value (90) and the Min Value (01) are signalled by a long Beep and Led L4=ON
To Memorize and Exit push contemporarily the buttons P1 and P2
The Controller goes in U9 Speed Setting: the Led L2 is blinking and L1=ON
In this condition the Controller manages the fan at the U9 Speed
Through the buttons P2 and P1 increase/decrease the fan speed
The Max Value (90) and the Min Value (01) are signalled by a long Beep and Led L4=ON
To Memorize and Exit push contemporarily the buttons P1 and P2
7.
SAFETY Function Enable
This function can only be enabled ONLY if Probe or Thermostat is used
Set the Controller in OFF (L4 ON) through the button P2
Remove the Line Power
Connect again the Line Power pushing contemporarily the button P2 for 5 seconds
The Controller goes in SAFETY Function Enable: the Led L2 is blinking
Through the buttons P2 and P1 enable/disable the SAFETY function:
L4 ON:
L4 OFF:
To Memorize and Exit push contemporarily the buttons P1 and P2
8.
Parameters Table
Code
A01
Fan Activation Thermostat
U1
U1 Fan Speed value
U9
U9 Fan Speed value
SIC
SAFETY Function Enable
Code
Default Parameters not modifiable
A02
SAFETY activation Thermostat
I01
A01 Thermostat Hysteresis
I02
A02 Thermostat Hysteresis
45°C (Long Beep)
50°C
55°C
60°C (Long Beep)
To Exit without Memorize Wait for 30 seconds
To Exit without memorize, wait for 30 seconds
Enabled Function
Disabled Function
To Exit without memorize, wait for 30 seconds
Description
U
Min
°C
40
n
1
n
1
--
0
U
Default
°C
100
°C
10
°C
10
Pag. 6 / 8
Default
Max
50
60
20
90
60
99
0