Módulo de actuador analógico, 4 canales

Publicidad

Idiomas disponibles

Idiomas disponibles

Z
Function
• The analog actuator module (extension module)
enlarges an KNX analog actuator by four analog
outputs which can be parameterized by means
of software.
• Received data are converted into the following
output signals: 0...1 V, 0...10 V, 0...20 mA or
4...20 mA.
• With these analog output signals, actuators
used for heating, ventilation and air conditioning
purposes are enabled to adapt their output
variables in acc. with informations received from
the bus and to be used within control processes.
• The output variables can be subject to forced
control.
• The module data as such and the forced-control
instructions are evaluated in the KNX analog
actuator
• The analog actuator module is connected to the
KNX device by means of a system connector
supplied with the device.
• Non used outputs can be deactivated.
• Voltage outputs are monitored for short-circuits.
• The output state is indicated by status LED.
Installation
The device is snap-fastened on a DIN rail 35 x 7,5
mm as per EN 50022.
G
The analog actuator module is connected to
an KNX analog actuator only by means of a
6-pole system connector (supplied with the
analog actuator module).
The
analog
actuator
module
external
24 V
power
supply
This unit can also supply the connected the
connected KNX analog actuator or other devices.
For easy connection, there are two pairs of internally
connected power supply terminals (marked by a
dot "•").
Connectable analog actuators
Safety warnings
• Do not connect electronic ballasts or
ç
electronic transformers with 1-10 V
control input to the outputs.
• Do not connect external voltages to the
outputs. Connected components must
ensure safe separation from other
voltages.
• The GND terminals must not be
connected with the terminals of the
same
designation
actuator (risk of irreparable damage!).
3
• Current outputs may be loaded with 500 Ω max.
• Voltage outputs must be loaded with 1 kΩ min.
• The GND terminals of outputs A1...A4 are
internally connected.
• In the event of a short-circuit between a voltage
output A1 ... A4 and GND, the respective output
is deactivated.
Wiring diagram
needs
an
230 V v
for
operation.
50/60 Hz
Connection
GND
: reference potential for outputs A1 ... A4
A1 ... A4 : analog outputs
24 V v : external supply voltage
A : devices with analog interface
B : status LED of the analog actuator module, red
C : status LEDs of the four analog outputs, yellow
D : system connector, 6-pole, for module
connection
E : system connector, 6-pole, for future
extensions
of
an
analog
U/I
U/I
U/I
U/I
GND
A1
GND
A2
GND
A3
GND
A4
TYF684E
A1...A4 :
DC 0-10 V
M
0(4)-20 mA
Status
A1
A2 A3 A4
AC 24 V
AC 24 V
24 V v
24 V v
Installation of an analog actuator
module
During the installation of an analog actuator module
the following basic rules must be observed:
• An analog output module can be replaced by one
of the same type (e.g. in case of defect) while the
system is in operation (disconnect voltage supply
from module!). After the replacement, the analog
actuator makes a reset after abt. 25 s. This action
re-initializes all outputs of the analog actuator
and of the connected modules and resets them
to their original state.
• Removal or addition of modules without adapting
the project and subsequent downloading into the
analog actuator is not permitted as this will result
in system malfunctions.
Status LED
Device status (red)
- Commissioning of the module
On
Module ready for operation
(self-test OK).
Quickly blinking
Module initialization in
progress
Slowly blinking
Module not confi gured (in
KNX device)
Off
Module initialized and in
operation
Precondition: LED must have
been on beforehand!
- Normal operation
On
Module
not
operation (fault)
Off
Modul initialized and in
operation.
Precondition: LED must have
been on beforehand!
Slowly blinking = 1/s; quickly blinking = 2/s
Output signals A1 ... A4 (yellow)
LED off : output signal is equal to zero
LED on : output signal is greater than zero.
ready
for
6T7659A