Idiomas disponibles

Idiomas disponibles

4B - INSTALLATION FOR TWO LOCATION CONTROL
Connect wires per wiring diagram as follows:
1. Connect green ground or bare copper wire in the wall box to the
Green wire of the device.
2. Connect Hot wire in the wall box to the Black wire of the device.
3. Connect Load wire(s) and Traveler wire in the wall box wire to
the Red wire of the device.
4. Screw wire connectors on clockwise making sure no bare
conductors show below the wire connectors. Secure each
connector with electrical tape.
5. Mount device in the wall box with screws and mount wall plate.
6. Repeat step 1-6 for installing another sensor switch to the wires
in the wall box. (the load wire may only exists in one wall box)
7. Restore power at circuit breaker or fuse. Installation is complete.
8. Turn on the power, manually press the switch button to check
whether the product is installed correctly, and at the same time
ensure that the LED light in the fresnel lens flashes. Wait about
40s for product booting, the product will work properly.
Neutral
Green
Hot
Black
Ground
Red
Traveler
Load
Wall Box 1
Hot (Black)
Black
Red
Red
Black
Line 120VAC, 60HZ
Green
Wall Box 1
Ground
Neutral (White)
NOTE:
1. Either sensor can turn the lights ON.
2. Either sensor must time-out to OFF, or both manual buttons
must be pressed for the lights to turn OFF.
3. A ground connection is required to operate. Use the ground
wire in the wall box for ground connection. If no ground is
available, consult an electrician. Device will not function if it is
not grounded.
4. The hot (black wire) and load (red wire) must be correctly
connected as stated above, otherwise the device will not
function. If the light never turns on, then try to reverse the hot
and load wiring of either or both sensors.
PREPARATION FOR UNIT SETTING
1. Pry off the top cover with a slotted screwdriver.
2. Set 3 controls of TIME, SENSOR and LIGHT after cover is off.
TIME
Delay Time
TIME
Disable Automatic OFF function
Neutral
Green
Hot
0
Automatically turn off the light after 30 seconds
Black
Automatically turn off the light after 5 minutes
1
Ground
Automatically turn off the light after 15 minutes
2
Red
3
Automatically turn off the light after 30 minutes
Traveler
LIGHT
Wall Box 2
Disable Automatic ON function
1
Automatically turn on the light in dark environment
2
Automatically turn on the light in brighter environment than LIGHT 1
Black
Automatically turn on the light in any light environment, including
3
the bright day
Load
COVERAGE PATTERNS
Green
White
The sensor detects motion in areas up to 900 sq. ft. and up to 35
Ground
Wall Box 2
feet from the sensor. Ideally, the sensor is designed for small
amounts of motion in space up to 300 sq. ft. The fresnel lens on
the sensor is a multiple segment viewing lens with a field of view
of 180°. The sensor must have a clear view of the people in the
space in order to detect occupancy. Obstructions, such as
furniture blocking the sensor's lens, may prevent occupancy
detection.
4.0'
(1.2m)
Floor
Manual Switch
TIME
0
SENSOR
LIGHT
Fresnel Lens
Top Cover
(Manual Switch)
SENSOR
LIGHT
Sensor Sensitivity
Light Sensitivity
NOTE
NOTE
35'
15'
(10.7m)
Side View
Top View
(4.6m)
SETTING FOR DIFFERENT MODES
A. Automatic ON & Automatic OFF Mode:
1. Set human body SENSOR sensitivity as desired.
2. Set delay TIME to "0" (30 seconds), "1" (5 minutes), "2" (15
minutes) or "3" (30 minutes) as desired.
3. Set LIGHT sensitivity to "1", "2" or "3" as desired.
For LIGHT "1", it will automatically turn on the light only in dark
environment, like during the night.
For LIGHT "2", it will automatically turn on the light in brighter
environment than LIGHT "1".
For LIGHT "3", it will automatically turn on the light in any light
environment, including the bright day. (Default Setting: 30
seconds delay TIME, maximum SENSOR sensitivity, maximum
LIGHT sensitivity)
B. Manual ON & Automatic OFF Mode:
1. Set human body SENSOR sensitivity as desired.
2. Set delay TIME to "0" (30 seconds), "1" (5 minutes), "2" (15
minutes) or "3" (30 minutes) as desired.
3. Set LIGHT sensitivity fully counterclockwise to " • " to disable
automatic ON function.
C. Manual ON & Manual OFF Mode:
1. Set delay TIME fully counterclockwise to " • " to disable
automatic OFF function.
2. Set LIGHT sensitivity fully clockwise to "3".
Human body SENSOR function will be disabled automatically.

QUICK TEST

Set delay TIME to "0" to automatically turn off the light after 30
seconds and set LIGHT to " • " to disable light sensitivity, this
allows you to quickly check the sensor coverage area.
For Warranty Statement, Service Parts, Technical
Support, or to Register your product, please visit our
website or call:
In the United States - Broan.com 800-637-1453 or
NuTone.com 888-336-6151. In Canada - Broan.ca or
NuTone.ca 877-896-1119
35'
(10.7m)
Broan
Hartford, WI 53027
www.broan.com
www.nutone.com
800-558-1711
888-336-3948
1101846A

Publicidad

loading