Tarjeta de expansión 8e/4s relé

Publicidad

Idiomas disponibles

Idiomas disponibles

M54503 - EXP. CARD - 8I/4O relay
This is a descriptive manual of the procedure to insert and
confi gure the inputs/outputs expansion card (relay) of the
CVMk2.
You can download the complete manual in digital format
from www.circutor.es
Before any maintenance, modifi cation to the
connections, repair, etc., the equipment must
be disconnected from the supply and the
measure connections. If wrong operation is
suspected the equipment must remain out of service. The
equipment is designed to changed quickly in the event
of any breakdown.
1. CARD INSTALLATION
Disconnect from supply and measure the device.
Remove the screw and the cover
Insert the card in the guides.
Press the card carefully.
Put the cover and the screw.
2. CARD SELECTION
When we have introduced the card, we have to confi gure it.
MENU
Select
from the upper line of the display and confi rm
SET
with
to unfold the window.
SETUP
SET
Select
and confi rm with
move in the upper menu with the arrows since
SET
and select it with
key.
CARD 1
CARD 2
We have 3 options (
,
to select according the position which we have introduced
the card. In the picture is position 1, then we will select
CARD 1
.
NOTE: If select you select a position where is no card, will
NO CARD
appear the message
.
When we have selected the card we have to confi rm with
SET
the
key and will enter in the alarm screen. (Section
2.1).
2.1. ALARM CONFIGURATIONS
The parameters of the alarms confi guration have double
meaning depending on the electrical variable selected in
VAR.CODE
(It is not advisable to schedule output pulses with relay).
ALARM 01
Alarm 1:
Var.Code
:
a). This is the code of electrical variable which we want
assign one alarm (see variable codes table).
b). Select one energy variable (f.e. 129 Active energy)
MAximUM
:
a). Maximum value of the variable to active the alarm.
b). This is the pulse value of this alarm.
Example:
W•h.
MINIMUM:
a). Mínimum value of the variable to active the alarm.
b). This value has no sense with energy parameter.
Delay ON
a). Minimum time (in seconds) that the condition has to be
true to activate the alarm.
b). Number of blocs of 10 ms that will be activated the
alarm to generate the pulse ON.
Example:
ms.
Delay OFF
a). Minimum time (in seconds) the condition has to be false
to deactivate the alarm.
b). Number of bloqs of 10 ms that will be deactivated the
alarm to generate the pulse OFF.
NEXT
The key
next
we push
The ecuations are the physical outputs of the device. From
OUT 01
to
We can go to
(Section 2.3)
2.2. OUTPUTS CONFIGURATION
To confi gure the outputs we have to implement the equation
line with the alarms codes that we have confi gured in the
section 2.1
We can configure the equations with AND &/or OR
functions between one or more alarms.
We can confi gure the equations with one or more of the
16 alarms formed before in the section 2.1, to activate
the outputs.
NEXT
Press
Consult complet manual to program output equations.
2.3. INPUTS CONFIGURATIONS
We can confi gure the inputs in two different ways:
WeighT
a).
This way confi gures the input as ON/OFF. No matter the
key. Now, we have to
decimal point.
EXP.CARD
WeighT
b).
CARD 3
or
). We have
This way confi gures the input as an increasing counter
(maximum counter value 10 M). The value multiplies each
input impulses.
Dec.Pos
:
This is the position of decimal point of the counter value.
If we press
08
.
M54503 - Expansión card 8I/4O relay -
section. We can classify in two groups:
a). Electrical Variable.
b). Energy Variable
000.010
. The alarm will be activated each 10
:
000010
. The alarm will be activated during 100
:
increases the screen since the alarm
again we will pass to the equations screen.
OUT 04
.
INPUTS
screen confi guration pressing
ALARM 01
to return to
confi guration.
0000
=
0000
NEXT
will increase the input number until
next
If press
again returns to
To go to alarms screens (section 2.1) we must press
in any INPUT screen.
3. CONNECTIONS
4. VARIABLE CODES
PARAMETER
Phase voltage
Current
Frequency
Active power
Inductive power
Capacitive power
Aparent power
F. P.
ϕ
Cos
All codes in complet manual of CVMk2
5. TECHNICAL CARACTERISTICS
16
. If
CHARACTERISTICS
INPUTS
Type
Type of connection
IN
key.
Vmax
minimum t
ON
minimum t
OFF
RELAY OUTPUT
Voltage A.C.
Current A.C.
Minimum load relay
Mechanical live
Electrical live
Connections
Wire section
6. TECNICAL ASSISTANCE SERVICE
In case of failure or any operational queries, please contact
the technical service of CIRCUTOR, SA.
TECNICAL ASSISTANCE SERVICE (TAS):
(+34) 93 745 29 00
CIRCUTOR, SA. – Aftersales service.
Vial Sant Jordi s/n
08232 Viladecavalls, Barcelona.
Tel.: (+34) 93 745 29 00
Fax: (+34) 93 745 29 14
e-mail: central@circutor.es
IN
CVM k 2
IN 01
.
OUT
L1
L2
L3
N
III
01
09
17
25
31
02
10
18
26
33
27
03
11
19
34
04
12
20
35
05
13
21
36
06
14
22
37
07
15
23
38
08
16
24
39
VALUE
UNIT
Free contact / NPN
Opto isolated
24
V c.c.
40
ms
40
ms
250
V a.c.
6
A a.c.
1
V a.c.
0,001
A a.c.
5x10
6
ciclos
NA:5x10
4
, NC:3x10
4
ciclos
0,05..1
mm
2
M98207601-20-08A