Address
read Description Input-Output
8432 Remote terminal temperature sensor
State On-Off
8528
0 = Off; 1 = On
8960 Regulation Probe
8962 Current Return Fan Speed
8963 Current Supply Fan Speed
8964 Three Point Cold or Changeover Valve
Estimated Position
Heater Status
8968
0 = Off; 1 = On
Pre Heater Status
8969
0 = Off; 1 = On
External Bypass Status
8970
0 = Off; 1 = On
8971 Outdoor Temperature
8975 Outlet Pressure
8976 Return air temperature
8977 CO2
8978 Expulsion Temperature
8987 On Off Status
8988 Boost Status
8990 Supply air temperature
Address
read Description Alarm
8991 Return air probe error
9000 Supply air probe error
9001 Fresh air probe error
9002 SKW Probe Error
9003 Filter Alarm
9006 Outlet Pressure Probe Error
9007 CO2 Probe Error
9008 Defrost/Expulsion Probe Error
9014 Antifreeze Alarm
9015 Fire Alarm (Manual Reset)
9017 Clock Error
9019 SKW Communication Alarm
Note:
(divided 10, °C) divide the value by 10, the result is in degree Celsius with one decimal place (Es: 175= 17.5°C)
(divided 10, %) divide the value by 10, the result is in percentage with one decimal place (Es: 505= 50.5%)
(HH:MM) minutes starting from midnight where 0= 00:00 e 1439= 23:59 (In example: 120= 02:00; 1170= 19:30)
firmware 0.26
Electronic Control "HRH-HRS" User Manual
Value
18.3
0
17.5
0.0
0.0
100.0
100.0
0
0
11.2
0
0
0
6.7
0
0
19.3
0= Not Active
1= Active
2=Manual Reset
Value
0
0
0
0
0
0
0
0
0
0
0
0
Um
Default
Min
°C
0
-500
0
0
°C
0
-500
%
0
0
%
0
0
%
0
0
%
0
0
0
0
0
0
°C
0
-500
Pa
°C
ppm
°C
-500
0
0
0
0
°C
0
-500
Um
Default
Min
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Rev.06
ENG
Max
1100
1
1100
1000
1000
1000
1000
1
1
1100
1100
1
1
1100
Max
1
1
1
1
1
1
1
1
1
2
1
1