Operation
7. UPS Battery Information
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x00BC
188
Battery voltage
0x00BD
189
Battery piece number
0x00BF
191
Battery capacity
0x00C0
192
Battery remain time
8. UPS Working Mode
Holding Register (Read Function 0x03)
Address
Hex
Decimal
Description
0x00D0
208
UPS Mode inquiry
9. UPS Fault Information
Holding Register (Range 0x02A3 - 0x02AE, Read Function 0x03)
Address
Hex
Decimal
Description
0x02A3
675
Fault type
0x02A4
676
Battery voltage before fault
0x02A5
677
I/P frequency before fault
0x02A6
678
I/P voltage before fault
0x02A7
679
Inverter O/P frequency before fault
0x02A8
680
Inverter O/P voltage before fault
0x02A9
681
Negative Bus voltage before fault
0x02AA
682
Positive Bus voltage before fault
0x02AB
683
O/P load before fault
0x02AC
684
O/P current before fault
0x02AD
685
Temperature before fault
0x02AE
686
UPS running status before fault
10. Setting Parameter Item
Holding Register (Read Function for 0x034A, 0x034B and 0x34E, Write Function 0x10 for range 0x034F - 0x351)
Address
Hex
Decimal
Description
0x034A
842
High efficiency mode voltage High Loss point
0x034B
843
High efficiency mode voltage Low Loss point
0x034E
846
The bypass Freq. High Loss point
The bypass Freq. Low Loss point (560, 580 or 590 for 60 Hz)
0x034F
847
(460, 480 or 490 for 50 Hz)
0x0350
848
The bypass voltage High Loss point (244, 254 or 264)
0x0351
849
The bypass voltage Low Loss point (176, 186 or 196)
*The unit must be in Bypass Mode for changes to take effect.
Unit
V
V
0.1 Hz
0.1 Hz
V
V
6
Unit
0.1V
%
Minutes
Unit
See Appendix 2
Unit
See Appendix 3
0.1V
0.1 Hz
0.1V
0.1 Hz
0.1V
0.1V
0.1A
0.1V
0.1V
0.1°C
See Appendix 4
Notes*
Type
N/A
Read Only
N/A
Read Only
N/A
Read Only
560
Read / Write
264
Read / Write
176
Read / Write