REGISTERS
SYSTEM REGISTERS
Register
Description
address
0
On/Off
1
Setpoint*
Room temperature
2
(Localtemp)**
Modes
3
4
Speeds
5
Louvres
6
Warnings
7
Errors
Notes:
(*) Maximum/Minimum limits depends on your A/C unit.
(**) Should be greater than 0.
Values
0 Off
1 On
Setpoint x 10
Example: 22.5 ºC 225
Localtemp x 10
Example: 22.5 ºC 225
1 Auto, 2 Cooling,
3 Heating, 4 Fan,
5 Dry
0 Auto, X SX (X: 1 - 7)
0 - 7 Louvres position
8 Auto
9 Swing
10 Swirl
Indoor unit warning code (4 digits ASCII code)
Indoor unit error code (4 digits ASCII code)
Operations
0x03, 0x04, 0x06, 0x10, 0x16
0x03, 0x04, 0x06, 0x10, 0x16
0x03, 0x04
0x03, 0x04, 0x06, 0x10, 0x16
0x03, 0x04, 0x06, 0x10, 0x16
0x03, 0x04, 0x06, 0x10, 0x16
0x03, 0x04
0x03, 0x04
ES
EN
FR
IT
PT
DE
17