Analog Photosensor 0-10 VDC
Photodétecteur analogique 0-10 Vc.c.
Fotosensor analógico de 0-10 VCC
General Information
The 0-10V analog photosensors are used in conjunction
with a Greengate controller that supports 0-10V analog
inputs. The photosensors provide a varying voltage to the
control panel dependent upon the light level seen by the
photosensor. The voltage returned is translated by the
controller into values which in turn may be programmed
to perform functions based on these values.
The analog photosensors are currently available in the
following models:
Catalog Number
PC-I
PC-O
PC-S
PC-A
PC-IS
Indoor
Outdoor
Photosensor
Photosensor
The analog photosensors connect to the control panel's
low voltage analog input channels. The lighting circuits
that are controlled by the photosensors as well as the
control strategies are determined by the programming
within the control panel. Refer to the individual control
panel's programming manual for information on
programming.
Model # PC-I, PC-O,
Model # PC-S, PC-A,
Model # PC-IS
Description
Indoor Photosensor
Outdoor Photosensor
Skylight Photosensor
Atrium Photosensor
Photosensor Daylighting Shield
Atrium/Skylight
Photosensor
Getting Started
1.
Do not discard these installation instructions. Please
keep for future reference and operation information.
2.
It is recommended that all low voltage wiring be
done with power removed to the logic board to
protect components from potential shorts during the
wiring process.
3.
Do not route low voltage wires with or near power
wiring. Bring analog wiring in through the low voltage
section of the lighting controller.
4.
Use only as intended and at the listed voltage.
5.
All installation and service must be performed by
qualified personnel or service technicians.
6.
Install in accordance with the National Electrical Code
and any other codes which may apply.
7 .
Installation and wiring information contained in this
document is based on industry accepted standards
and practices. If conflicts exist between these
instructions and any applicable codes or ordinances,
please contact Greengate before proceeding with the
installation.
8.
High voltage is present inside the enclosure. Use
extreme caution when performing maintenance on
this equipment.
9.
Document all wiring and device terminations and
locations so that devices can be properly configured
and programmed for operation.
INS #

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Greengate PC-I

  • Página 1 The 0-10V analog photosensors are used in conjunction with a Greengate controller that supports 0-10V analog It is recommended that all low voltage wiring be inputs. The photosensors provide a varying voltage to the...
  • Página 2 Snow Line mounting guidelines outlined in this document for your photosensor type. PC-I: Indoor Photosensor Mounting Mount the sensor in a 3/8” hole in the false ceiling tile fixing it in place with the adhesive backing. For daylight dimming applications with a CK4A, the photocell should be located so that it views indirect light from its controlled zone.
  • Página 3 Wiring the Photosensor to the Controller PC-S: Skylight Photosensor Mounting Wiring Locate the sensor indoors as near to the center of the skylight well as possible or at least 12 inches from the side. The sensor should be exposed to full daylight and not be put in a location that may be shadowed.
  • Página 4 Photosensor Daylighting Shield (Option) Photosensor Lower Upper Lower Upper Type Endpoint Endpoint Voltage Voltage PC-I (In-door) 0 fc. 100 fc. 1 Volt 10 Volt Double Sided Tape Attach to Cone of PC-O (Outdoor) 0 fc. 250 fc. 1 Volt 10 Volt Photosensor.
  • Página 5: Renseignements Généraux

    à tout autre code applicable. Les photodétecteurs analogiques 0-10V sont utilisés avec Les renseignements sur l'installation et le câblage qui un régulateur Greengate prenant en charge les entrées sont fournis dans ce document sont fondés sur des analogiques 0-10V. Ces photodétecteurs fournissent une normes et des pratiques reconnues dans l'industrie.
  • Página 6 Câblage du photodétecteur vers le régulateur Dans les deux applications, le détecteur doit être installé pour ne percevoir que la lumière réfléchie et non pas Verre d'atrium une source de lumière directe. Placez le détecteur dans un rayon de 152,4 m (500 pieds) environ du panneau de commande.
  • Página 7 Branchez le fil JAUNE sur l'une des bornes ANALOG IN 0 lm/m² 1076,39 lm/m² PC-I (en intérieur) 1 volt 10 volts (libellées AN1, AN2, AN3, AN4). (0 lm/pi²) (100 lm/pi²) 0 lm/m² 2690,98 lm/m²...
  • Página 8: Información General

    El voltaje u ordenanza aplicables, contacte a Greengate antes de devuelto es transformado en valores por el controlador, proceder con la instalación.
  • Página 9: Cableado Del Fotosensor Con El Controlador

    Cableado del fotosensor con el controlador En ambas aplicaciones, el sensor debe montarse de modo que mire a la luz reflejada solamente, no a ninguna fuente Vidrio del atrio de luz directa. Ubique el sensor dentro de 500 pies (152,40 m) de distancia del panel de control. PC-O: Montaje del fotosensor de exteriores Ubique el sensor en un techo o donde quede expuesto en su totalidad a la luz diurna.
  • Página 10: Pantalla Para Luz Diurna Del Fotosensor (Opcional)

    +24 VCC del conector de alimentación periférico. 0 pies-candela 100 pies-candela PC-I (en la (0 lumen/metro (1076,39 lumen/ 1 voltio 10 voltios puerta) 10. Conecte el cable AMARILLO con uno de los terminales...
  • Página 11 WARRANTIES AND LIMITATION OF LIABILITY Please refer to www.coopercontrol.com under the Legal section for our terms and conditions. GARANTIES ET LIMITATION DE LA RESPONSABILITÉ LÉGALE Veuillez consulter la section juridique de www.coopercontrol.com pour connaître nos conditions générales GARANTÍAS Y LIMITACIONES DE RESPONSABILIDAD CIVIL Remítase a la sección Legal del sitio web www.coopercontrol.com para conocer nuestros términos y condiciones.

Este manual también es adecuado para:

Pc-oPc-sPc-aPc-is

Tabla de contenido