OPTIMA-EX[GD]
Example of marking label EAC Ex
1Ex e IIC T5 Gb X 2017
Tamb. -50/+60°C
1Ex e IIC T6 Gb X
Tamb. -50/+50°C
Ex tb IIIC T80°C Db X IP66
THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE INSTALLATION
1. INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE.
1.1 SAFETY RULES.
OPTIMA-EX[GD] are designed as Group II Category 2 equipment and is suitable for use for fixed installation in areas with
explosion hazard designated Zone 1/21 and Zone 2/22. These operating instructions must be kept in safe place for later
consultation. Use OPTIMA-EX[GD] only for their intended duty in the undamaged and clean condition, and only where the
resistance of the material to the surroundings is assured. No modifications are allowed to the OPTIMA-EX[GD] that are not
expressly mentioned in this instruction manual. When installing the OPTIMA-EX[GD] the clearance and creepage distance shall
be duly considered as topic 5.3 (table).
The OPTIMA-EX[GD] are available in materials GRP with the following rated current 16A, 32A, 63A, 125A.
The plug series OPTIMA-EX[GD] have to be used only with SCAME socket series ADVANCE-GRP[GD], Ex db eb IIC / Ex tb IIIC ,
with separated certification. The ADVANCE-GRP[GD] socket switch-handle move a mechanical interlock mechanism that avoid
to separate the plug contacts from the plug outlet when the contacts are energized. The plug series OPTIMA-EX[GD] can be to
pull-out only when the handle is in position 0 (zero).

1.2 CONFORMITY TO STANDARDS

The socket OPTIMA-EX[GD] are designed for Zone 1/21 and Zone 2/22 according to :
• EN 60079-0:2012,
• EN 60079-7:2015,
• EN 60079-31:2014
• EN 60309-1:1999 +A1:2007, +A2:2012
• EN 60309-2:1999 +A1:2007, +A2:2012
• IEC 60079-0:2011,
• IEC 60079-7:2015,
• IEC 60079-31:2013
• IEC 60309-1:1999, +A1:2005, +A2:2012
• IEC 60309-2:1999, +A1:2005, +A2:2012
• ГОСТ 31610.0-2014, (IEC 60079-0:2011)
• ГОСТ Р МЭК 60079-7-2012
• ГОСТ IEC 60079-31-2010
They are manufactured and tested in accordance with ATEX directive 2014/34/EU, IECEx scheme, EAC Ex certification, state-of-
the-art engineering practice and ISO 9001.
MP39684
Via Costa Erta, 15 - 24020 Parre (BG) Italy
0051
219.1633.RU
II 2GD
2P+T 16A
6h 200-250V
11
BHИМАНИЕ
Teмnepaтypa кaбeля 80°C,
когда максимум
Ta составляет +60°C
HAHИO ЦCBЭ
№ TC RU C-IT.AA87.B.00XXX
ZP90905-5