D- USING YOUR PRODUCT
Product Settings
Water Level Setting
During production, water level for water determination is fixed.
When necessary or if it is necessary to set again, the float must not be rotated without loosening the
screws of the micro button.
If water level is too low, ice cubes bar be very large.
If the water level is too high, ice bars will form under the evaporator and therefore ice cubes stick each
other and cannot free fall.
Right water level is in a way that about two (2) mm of water remains from the top.
Pressurestat Setting
The pressurestat controls pressure by starting or stopping fan. Thus, the pressure difference is kept
constant (2.5 kg/cm2 – 120 – 125 psig).
In a pressure value under this level, it will be difficult to separate ice cubes from each other. Under a
pressure value above this value, production capacity decreases and operating life of the compressor
shortens
EN
NOTE
Clockwise rotation causes increase in pressure. One rotation equals to the pressure value of about 1.5 kg/
cm2 (=22 psig)
34