Schematic Diagram for Direct On-line Starters
K1M
K1M
3-phase
2-phase
WARNING:
Bonding between metallic
conduits must be provided.
AVERTISSEMENT:
Une liaison électrique
doit être assurée entre les conduits
métalliques.
BONDING CONDUCTOR
SUPPLY CONDUCTOR
SIZE (AWG)
QTY.
14
1
12
1
10
2
FOR USE WITH SPRECHER+SCHUH
GROUNDING ADAPTER KIT, CAT. NO. KS7-GR1
SEE APPLICABLE CODES AND LAW
FOR GROUNDING REQUIREMENTS
Dimensions
125 [4.93]
3.5 [0.14]
30 [1.18]
88.6 [3.49]
125 [4.93]
50 [1.97]
DIR 10000753238 (Version 00)
Printed in Estonia
2
1
K1M
K1M
Single-phase
Impulse Control
Multi Function Push Button
Add wires for common control. Remove if separate control is required.
L1 Control voltage supplied from external source.
Wiring Tables
Impulse Control
From
K1M - A2
SIZE
14
K1M - A1
12
12
S1 - 14
F2 - 95
Ø23
[Ø0.91]
50 [1.97]
2
K1M
Maintained Control
O - I Selector Switch
Maintained Control
To
Length [mm]
From
( N )
280
K1M - A2
K1M - 13
100
K1M - A1
S1 - 13
140
S1 - 14
S1 - 31
100
K1M - 14
140
S1 - 32
140
125 [4.93]
Pozidriv No. 2
Pozidriv No. 2
(1.2 x 6.5)
(1.2 x 6.5)
2.0 Nm
2.0 Nm
18 lb-in
18 lb-in
To
Length [mm]
( N )
280
S1 - 13
140
F2 - 95
140
16
[0.63]
110 [4.33]
Rotary operator alternatively
(for maintained control)
28.1 [1.11]
10
10
Pozidriv No. 2
Pozidriv No. 2
2 x 1...6 mm²
2 x 1...6 mm²
2 x No. 14...10 AWG
2 x No. 14...10 AWG
L1
1
2
96
97
95
98
1 When E-STOP is used
L1
2 WIRE
CONTROL
2
2
1
3
1
1
1- HAND
2- OFF
3- AUTO
A1
A2
Illuminated HOA Selector Switch
2.3 Nm
2.3 Nm
20 lb-in
20 lb-in