Installation Instructions
MDB Series Fuseholder / Power Distribution Module
Part Numbers: 04980932.X, 04980932ZXT, 04980933.X, and 04980933ZXT
Assembly Instructions
Please Note: Size your fuses so that your continuous
load rating = ~75% of the fuse rating.
For example: If your load is 60A use an 80A fuse
1. Unlatch yellow clips (this may require a small flat
head screwdriver) and remove cover
2. Optional – secure spare fuses to inside of cover
with small screws
3. Place MIDI
fuses into holder with terminals flush
®
to bottom of the holder. Make sure that they are in
correct location for your application
4. Place the bus bar directly on top of the fuses.
5. Put the wire through the cap, then apply the
grommet, then crimp on an appropriate sized M5
ring terminal. This should be done for the input and
all output cables
6. Place the wires through the appropriate openings
and onto the studs. Slide the grommets up on
all cables and seat them into the openings of the
holder. This should be done for the input and all
output cables
7 . Snap the caps into place to help secure the
grommets. This should be done for the input and all
output cables
8. Screw down all the flange nuts to 5 Nm torque
9. Replace the cover on the box making sure that the
cover is fitted correctly and the seal is not being
pinched or damaged
10. Snap the AssureLatch™ yellow clips closed to
ASSURE that the unit is properly sealed. If you
cannot snap the clips closed it means that the cover
is not correctly placed and the unit is not sealed.
Check to make sure that the cover is correctly
aligned and pressed completely onto the base.
Attention: Choose M5 terminals that will fit through
the openings in the housings.
Do not crimp on the ring terminals until the caps and
grommets are applied!
Maximum Terminal Size
© 2020 Littelfuse Commercial Vehicle Products
littelfuse.com
Input
3 Output
Dimension
Opening
Openings
A Max
14.0 mm
12.25 mm
Mounting
• M6 or ¼" Mounting Bolts or a post in one location to poka-
yoke assembly
• Leave room to allow AssureLatches™ to open so that
fuses are serviceable.
Minimum Bend Radius
• 25 mm2 (4AWG) cable minimum radius > 40mm
• 16 mm2 (6AWG) cable minimum radius > 30 mm
• 10 mm2 (8AWG) cable minimum radius > 20 mm
• 6 mm2 (10AWG) cable minimum radius > 15 mm
If these (bend radius) recommendations are not followed,
then seal integrity may be compromised and module will not
be waterproof
Use Strain Relief: Cabling should be secured from moving
once the MDB is installed.
1 of 4
IF-176
Rev: 011420-B

Publicidad

loading

Resumen de contenidos para Littelfuse MDB Serie

  • Página 1 Input 3 Output Dimension Opening Openings Use Strain Relief: Cabling should be secured from moving A Max once the MDB is installed. 14.0 mm 12.25 mm 1 of 4 © 2020 Littelfuse Commercial Vehicle Products IF-176 Rev: 011420-B littelfuse.com...
  • Página 2 Alivio de tensión de uso: El cableado debe asegurarse para que ¡No engarce los terminales de anillo hasta que se no se mueva después de instalar el portafusibles serie MDB. coloquen las tapas y las arandelas! 2 of 4 © 2020 Littelfuse Commercial Vehicle Products IF-176 Rev: 011420-B littelfuse.com...
  • Página 3 à l’eau. Utiliser un dispositif antitraction : Une fois le porte-fusibles MDB installé, utiliser un dispositif antitraction pour empêcher les câbles de bouger. 3 of 4 © 2020 Littelfuse Commercial Vehicle Products IF-176 Rev: 011420-B littelfuse.com...
  • Página 4 Étape 3 Étape 8 Étape 5 Paso 4 Étape 4 Step 6 Step 7 Paso 6 Paso 7 Étape 6 Étape 7 Step 10 Paso 10 Étape 10 4 of 4 © 2020 Littelfuse Commercial Vehicle Products IF-176 Rev: 011420-B littelfuse.com...

Este manual también es adecuado para:

04980932.x04980932zxt04980933.x04980933zxt