EXTERNAL TWILIGHT SWITCH
with internal probe
art. 1IC7242
Operation threshold
ENGLISH
from 2 to 200 LUX ad ustable
1 - TECHNICAL DATA
Caracteristics of the breaking device:
Example of maximum operating power:
2300 W (23
lamps
x 100W)
700 W (12 lamps x 58W)
2 - OVERALL DIMENSIONS
4 - INSTALLATION PROCEDURE
Note for the installer: provide adequate wiring trunking (particularly
for the power supply voltage), respecting the system standard in force.
5 - ELECTRICAL CONNECTIONS
Caution: if the load is particularly reactive (e.g. discharge, fluorescent,
electronic lamps, etc.) or its cos is lower than those indicted in the
technical data, the relay could be damaged.
In this cases use an external relay or contactor with suitable properties.
6 - OPERATION THRESHOLD AD USTMENT (LUX)
With shield removed, electrical connections made and power supply ON, make the
adjustment (from 2 to 200 LUX) working with a small screwdriver on the trimmer of
adjustment threshold (see figure).
The green LED lights up to indicate that the threshold is activated.
7 - MODE OF OPERATION
The external twilight switch manages the switching ON and OFF of external lighting system.
The switch closes the contact when the brightness of the surroundings drops below the
threshold set and keeps it closed until the threshold is passed.
For correct operation, the twilight switch must be installed so that it is not influenced by the
switching ON of the lamps to which it is connected or however by any other light source
(commercial signs, vehicle lights, etc.)
2
j
290 W (5
lamps
x 58W 35 µF)
Photodiode
3 - DESCRIPTION
SHIELD FASTENING SREWS
J
The manufacturer reserves the right to make all technical and manufacturing
Read this manual carefully before using the
product as it provides important guidelines
regarding safety, installation and use. The
manual must be preserved with care for future
reference.
16A / 5
2 0V~
engineers and
standards and laws in force.
T h e m a n u f a c t u r e r a s s u m e s n o
CFL
LED
responsibility for the use of products which
must follow particular standards of
max 7 lamps (7W ÷ 15W)
surroundings and/or installation.
This symbol on the product or its packaging to indicates
that this product shall not be treated as household waste.
Instead, it shall be handed over to the applicable collection
point for the recycling of electrical and electronic
equipment, such as for example:
- sales points, in case you buy a new and similar product;
- local collection points (waste collection centre, local
recycling center, etc...).
SHIELD
By ensuring this product is disposed of correctly, you will
help prevent potential negative consequence for the
environment and human health, which could otherwise be
GASKET
caused by inappropriate waste handing of this product.
The recycling of materials will help to conserve natural
resources. For more detailed information about recycling
of this product, please contact your local city office, your
CABLE GLANDS-CABLE CLAMPS
house hold waste disposal service or the shop where you
purchased the product.
This photocell lighting control
switch must be protected
against overload and / or short
circuit by with a thermal
magnetic switch type C with max
rated current
max
10
A
N
230V~
L
WARNINGS!
IMPORTANT
the devices and apparatus must
be installed and electrically
connected by qualified
i
n conformity with the
Before starting any operations on
the device, disconnect the 230V~
mains power supply
DISPOSAL OF ELECTRICAL
& ELECTRONIC EQUIPMENT
.
4 ÷ 9 mm
modifications deemed necessary without prior notice.