For Installer; Installer Setup System Setup; Optional Pcb Connectivity; Zone & Sensor - Panasonic WH-ADC0309J3E5C Instrucciones De Funcionamiento

Ocultar thumbs Ver también para WH-ADC0309J3E5C:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 40
Menus

For installer

Menu

5 Installer setup System setup

Optional PCB connectivity

5.1
To connect to the external PCB
required for servicing.
• If the external PCB is connected (optional), the system will have following additional functions:
Buffer tank connection and control over its function and temperature.
1
Control over 2 zones (including the swimming pool and the function to heat water in it).
2
Solar function (the solar thermal panels connected to either the DHW (Domestic Hot Water) Tank or the Buffer Tank.
3
• DHW is not applicable for WH-ADC *models.
External compressor switch.
4
External error signal.
5
SG ready control.
6
Demand control.
7
Heat-Cool SW
8
Zone & Sensor
5.2
To select the sensors and to
select either 1 zone or 2 zone
system.

Heater capacity

5.3
To reduce the heater power if
unnecessary.*
3 kW / 6 kW / 9kW
* Options of kW vary depending
on the model.

Anti freezing

5.4
To activate or deactivate the
water freeze prevention when
the system is OFF
5.5

DHW capacity

To select tank heating capacity
to variable or standard. Variable
capacity heat up tank with
fast mode and keep the tank
temperature with effi cient mode.
While standard capacity heat up
tank with rated heating capacity.
24
Default Setting
Setting Options / Display
No
Zone
• After selecting 1 or 2 zone system, proceed
to the selection of room or swimming pool.
• If the swimming pool is selected, the
temperature must be selected for
T temperature between 0°C ~ 10 °C.
Sensor
* For room thermostat, there is a further
selection of external or internal.
Yes
Variable

Publicidad

Tabla de contenido
loading

Tabla de contenido