Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23

Enlaces rápidos

1)
Introduction
The BExDS120D and BExDS110D are flameproof sounders
which are certified to meet the requirements of the ATEX
directive 94/9/EC and the IECEx scheme. The sounders
produce loud warning signals and can be used in hazardous
areas where potentially flammable gas and dust atmospheres
may be present. Thirty-two different first stage alarm sounds
can be selected by internal switches, and each one can be
externally changed to a second or third stage alarm sound
(see tone table on Page 4). The BExDS120D unit produces
output levels in the 117dB(A) range and the BExDS110D unit
produces output levels in the 110dB(A) range. Both sounders
can be used in Zone 1 and Zone 2 areas with gases in groups
IIA, IIB and IIC and temperature Classifications of T1, T2, T3
and T4. For ambient temperatures over +55ºC the gas groups
are limited to IIA and IIB. They can also be used in Zone 21
and Zone 22 areas for combustible dusts and have an IP rating
of IP 67 and a surface temperature rating of T100ºC up to
+55ºC and T115ºC over +55ºC.
2)
Marking
All units have a rating label, which carries the following
important information:-
Input Voltage:
DC Units
AC Units
Codes:
Ex d IIC T4 for Ta –50°C to +55ºC
Ex d IIB T4 for Ta –50°C to +70ºC
Ex tD A21 IP67 T115°C based on max Ta of +70°C
KEMA 99ATEX6312
Certificate No's
IECEx KEM 10.0003
Epsilon x:
Equipment Group and
Category:
CE Marking:
Notified Body No.
"Warnings
"
DO NOT OPEN WHEN AN EXPLOSIVE
GAS OR DUST ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS
(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC
Year of Construction /
Serial No.
3)
Type Approval Standards
The sounders have EC Type Examination and IECEx
certificates issued by KEMA and have been approved to the
following standards:-
__________________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. IS 2451-P
Issue E
INSTRUCTION MANUAL (ATEX / IECEx)
For use in Flammable Gas and Dust Atmospheres
12V or 24V or 48V
230V or 110V or 115V
II 2G/D
0518
i.e. 10 / 1DS22000001
19-02-10
BExDS120D and BExDS110D
Flameproof Sounders
EN60079-0:2006 IEC60079-0:2004 (Ed4)
EN60079-1:2007 IEC60079-1:2007 (Ed6)
EN61241-0:2006 IEC61241-0:2004 (Ed1)
EN61241-1:2004 IEC60079-1:2004 (Ed1)
4)
Installation Requirements
The sounders must be installed in accordance with the latest
issues of the relevant parts of the EN60079 standards or the
equivalent IEC standards –
maintenance of electrical apparatus for use in potentially
explosive atmospheres (other than mining applications or
explosive processing and manufacture):-
EN60079-14:2008
IEC60079-14:2007 (Ed4)
EN60079-10:2003
IEC60079-10:2008 (Ed1)
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried out
by a competent electrical engineer who has the necessary
training.
5)
Zones, Gas Group, Category, IP Rating and
Temperature Classification
The BExDS120D and BExDS110D sounders have been
certified Ex de IIC T4 for Ta –50°C to +55ºC and Ex de IIB T4
for Ta –50°C to +70ºC for gas and Ex tD A21 IP67 T115ºC
based on max. Ta of +70ºC for dust. This means that the units
can be installed in locations with the following conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA
Group IIB
Group IIC (Up to +55ºC only)
Temperature Classification:
sales@e-2-s.com
www.e-2-s.com
Sheet 1 of 4
General Requirements
Flameproof Enclosure 'd'
Dust General
Requirements
Dust Enclosures tD
Selection, Installation and
Electrical Installations in Hazardous
Areas (other than mines)
Classification of Hazardous Areas
Propane
Ethylene
Hydrogen and Acetylene
o
T1
400
C
o
T2
300
C
o
T3
200
C
o
T4
135
C
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200
(1)

Publicidad

Tabla de contenido
loading

Resumen de contenidos para E2S BEDS120D Serie

  • Página 1 INSTRUCTION MANUAL (ATEX / IECEx) BExDS120D and BExDS110D Flameproof Sounders For use in Flammable Gas and Dust Atmospheres Introduction The BExDS120D and BExDS110D are flameproof sounders EN60079-0:2006 IEC60079-0:2004 (Ed4) General Requirements which are certified to meet the requirements of the ATEX EN60079-1:2007 IEC60079-1:2007 (Ed6) Flameproof Enclosure ‘d’...
  • Página 2 Area Classification Dust: On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation. Also Zone 21 Explosive dust air mixture likely to occur in check that the earth bonding wire between the two casting normal operation.
  • Página 3 The above table also shows the maximum voltages at which used and also meet the requirements of the Ex ‘d’ flameproof the sounders can be operated. installation standard EN60079-14:2008 / IEC60079-14:2007. W hen only one cable entry is used the other one must be Cable Selection closed with an Ex ‘d’...
  • Página 4: Volume Control

    care should be taken to dress the wire so that when the cover AC Units Second and Third Stage Tone Selection is inserted into the chamber the wires do not exert excess To select the second and third stage tones on the BExDS120D pressure on the terminal blocks.
  • Página 5: Installation Requirements

    INSTRUCTION MANUAL (ATEX / IECEx) (GBR) BExDS120D and BExDS110D Flameproof Sounders For use in Flammable Gas and Dust Atmospheres 2) Marking Gas Groupings: All units have a rating label, which carries the following important information:- Group IIA Propane Group IIB Ethylene BExDS120D or BExDS110D Unit Type No.
  • Página 6 BExDS120D 110V AC 200mA 121V See drawing C and D BExDS120D 115V AC 180mA 126V Tone Selection and 2nd and 3rd Stage Alarms BExDS110D 24V DC 265mA BExDS110D 12V DC 195mA See wiring diagram E BExDS110D 48V DC 130mA BExDS110D 230V AC 56mA 264V...
  • Página 7 Drawing A Drawing C Loosen screw to adjust. Lossen screw Løsn skruen for at tilpasse. to adjust Schroef losdraaien om af te stellen. Desserrer la vis pour régler. Zum Regulieren Schraube lockern. Allentare la vite per poter effettuare la regolazione. Løsne skruen for å...
  • Página 8 Wiring Diagram E BExS120D and BExS110D DC Units S2 S3 S2 S3 S2 S3 BExS120D and BExS110D AC Units C S2 S3 C S2 S3 C S2 S3 Drawing F BExS120D BExS110D _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e-2-s.com Tel: +44 (0)208 743 8880 www.e-2-s.com...
  • Página 9 INSTRUKTIONSMANUAL (ATEX / IECEx) (DNK) BExDS120D og BExDS110D Flammesikre soundere Til brug i miljøer med brandfarlige gasser og 2) Mærkater Gasgrupperinger: Alle enheder har en klassificeringsmærkat, der bærer Gruppe IIA Propan følgende vigtige oplysninger: Gruppe IIB Ethylen Gruppe IIC < +55ºC Hydrogen og acetylen BExDS120D eller BExDS110D Enhedstypenr.
  • Página 10 BExDS110D 24V DC 265mA Tonevalg og 2. og 3. niveau alarmer BExDS110D 12V DC 195mA BExDS110D 48V DC 130mA Se ledningsdiagram E BExDS110D 230V AC 56mA 264V BExDS110D 110V AC 93mA 121V BExDS110D 115V AC 110mA 126V Volumenkontrol Ovenstående tabel viser også maksimalspændingen, som Se illustration F sounderne kan betjenes ved.
  • Página 11 INSTRUCTIEHANDLEIDING (ATEX / IECEx) (NLD) BExDS120D en BExDS110D Vuurvaste alarmgevers Voor gebruik in brandbare gas- en stofatmosferen 2) Labels Alle eenheden zijn voorzien van een label, waarop de Gasgroeperingen: volgende belangrijke informatie staat: Groep IIA Propaan BExDS120D of BExDS110D Typenr. eenheid: Groep IIB Ethyleen Groep IIC <...
  • Página 12 gebruikt, met een nominale werktemperatuur van ten minste BExDS120D 230 V AC 90 mA 264 V 110º C. BExDS120D 110 V AC 200 mA 121 V BExDS120D 115 V AC 180 mA 126 V 12) Kabelaansluitingen BExDS110D 24 V DC 265 mA 30 V Zie tekening C en D...
  • Página 13: Alarmes Sonores Antidéflagrantes

    MANUEL D’UTILISATION (ATEX / IECEx) (FRA) Alarmes sonores antidéflagrantes BExDS120D et BExDS110D Pour une utilisation dans des atmosphères poussiéreuses et contenant des gaz inflammables 2) Marquage Les caractéristiques nominales de toutes les unités figurent Zone 2 Mélange d’air et de gaz explosif ne pouvant sur une étiquette comportant les informations importantes pas survenir et qui, dans le cas contraire, suivantes :...
  • Página 14 Type d’unité Tension Courant Volts I/P +40ºC, la température d’entrée du câble peut excéder +70ºC d'entrée d’entrée max. et des câbles résistants à la chaleur doivent être utilisés, d’une température de service assignée de 110ºC minimum. BExDS120D 24 V CC 800 mA 30 V BExDS120D...
  • Página 15 TECHNISCHE HINWEISE (ATEX / IECEx) (DEU) BExDS120D und BExDS110D Schwer entflammbare Sounder Zum Einsatz in entflammbaren Gas- und Staubatmosphären 2) Kennzeichnung Zone 2 Explosive Gas-Luft-Mischung unwahrschein- Alle Geräte sind mit einem Typenschild mit den folgenden lich und sollte sie doch auftreten, dann nur wichtigen Informationen versehen:- kurzfristig.
  • Página 16 BExDS110D 12V DC 195 mA Siehe Zeichnung Cund D BExDS110D 48V DC 130 mA Tonwahl und Alarm der 2. und 3. Stufe BExDS110D 230V AC 56 mA 264V BExDS110D 110V AC 93 mA 121V Siehe Schaltbild E BExDS110D 115V AC 110 mA 126V Lautstärkeregulierung...
  • Página 17: Requisiti Di Installazione

    MANUALE DI ISTRUZIONI (ATEX / IECEx) (ITA) Sirene antincendio BExDS120D e BExDS110D Per l'utilizzo in atmosfere di gas e polveri infiammabili 2) Marchio Gruppi di gas: Tutte le unità sono dotate di etichetta contenente le seguenti importanti informazioni:- Gruppo IIA Propano Gruppo IIB Etilene...
  • Página 18: Controllo Del Volume

    BExDS120D 230 V CA 90 mA 264 V BExDS120D 110 V CA 200 mA 121 V 12) Connessioni dei cavi BExDS120D 115 V CA 180 mA 126 V Vedere figura C e D BExDS110D 24 V CC 265 mA 30 V BExDS110D 12 V CC 195 mA...
  • Página 19 INSTRUKSJONSHÅNDBOK (ATEX / IECEx) (NOR) BExDS120D og BExDS110D Flammesikre lydalarmer For bruk i atmosfærer med brennbar gass og brennbart støv 2) Merking Alle enheter har en etikett med følgende viktige informasjon: Gassgrupperinger: BExDS120D eller BExDS110D Enhetstypenr. Gruppe IIA Propan Gruppe IIB Etylen Inngangsspenning: DC-enheter 12 V eller 24 V eller 48 V Gruppe IIC <...
  • Página 20 Enhetstype Inngangs- Inngangs- Maks Tonevalg og 2.- og 3.-trinnsalarmer spenning strøm I/P volt Se kablingsskjemaet. E BExDS120D 24 V DC 800 mA 30 V BExDS120D 12 V DC 850 mA 15 V Volumkontroll BExDS120D 48 V DC 420 mA 58 V BExDS120D 230 V AC 90 mA...
  • Página 21 MANUAL DE INSTRUÇÕES (ATEX / IECEx) (PRT) BExDS120D e BExDS110D Sirenes à Prova de Fogo Para utilização em Atmosferas Inflamáveis de Gás e Poeiras 2) Marcação Grupos de gases: Todas as unidades têm uma placa de especificações com a seguinte informação importante: Grupo IIA Propano Grupo IIB...
  • Página 22: Controlo Do Volume

    BExDS120D 24V CC 800mA entrada do cabo pode exceder os +70º C e, por isso, devem BExDS120D 12V CC 850mA usar-se tubos resistentes ao calor, com uma capacidade de BExDS120D 48V CC 420mA temperatura de serviço nunca inferior a 110º C. BExDS120D 230V CA 90mA...
  • Página 23 MANUAL DE INSTRUCCIONES (ATEX / IECEx) (ESP) Sondas acústicas antideflagrantes BExDS120D y BExDS110D Para su utilización en ambientes con polvo y gases inflamables 2) Marcas Grupos de gas: Todas las unidades llevan una etiqueta de clasificación con la siguiente información importante: - Grupo IIA Propano Grupo IIB...
  • Página 24: Conexiones De Los Cables

    Tipo de unidad Voltaje Corriente IP máx de entrada del cable puede superar +70ºC;por lo tanto, entrada entrada volts deben usarse casquillos de cable resistentes al calor adecuados, con una temperatura de servicio nominal de al BExDS120D 24V CC 800mA menos 110ºC.
  • Página 25 INSTRUKTIONSBOK (ATEX / IECEx) (SWE) BExDS120D och BExDS110D Varningsljud for explosionsfarligt utrymme För användning i antändliga gas- och dammatmosfärer 2) Märkning Samtliga enheter är försedda med märkplåt med följande Explosionsgrupper: viktiga information: Grupp IIA Propan BExDS120D eller BExDS110D Typ: Grupp IIB Etylen Grupp IIC <...
  • Página 26 Ingångsspänning Ingångsström Max. Se ritning C och D spänning Tonval och 2- och 3-lägeslarm BExDS120D 24V DC 800mA Se kopplingsschema. E BExDS120D 12V DC 850mA BExDS120D 48V DC 420mA BExDS120D 230V AC 90mA 264V Volymkontroll BExDS120D 110V AC 200mA 121V BExDS120D 115V AC 180mA...
  • Página 27: Ec Declaration Of Conformity

    Date and Place of Issue: London, 04/07/2012 Quality Assurance Manager Document No: DC-001-Issue_C Telephone: +44 (0)20 8743 8880 European Safety Systems Ltd Facsimile: +44 (0)20 8740 4200 Company Registration No. 2763350 E-mail: sales@e2s.com Registered Office: Impress House www.e2s.com Mansell Road, London, UK, W3 7QH, UK...

Este manual también es adecuado para:

Beds110d serie

Tabla de contenido