Typical protection configurations for various power distribution systems are given below.
TN-C Network System, 3+0
F1
L1
L2
L3
PEN
F2
Back - up fuse
per IEC
Protection against short circuit
L
S1
F1
F1 ≤ 250A gG
F2
F2 not needed
F1
≤ 40A
63A —80A
F2
-
-
2
2
S1
6mm
10mm
S2
2
2
S2
6mm
10mm
Fault Indication
Green
OFF
ON
Dimensions
2.13 [54]
max. 2.7 [70]
L1
L2
L3
PEN
Neutral Conductor
PE Conductor
i
PEN Conductor
Isccr = 50kA
Isccr = 25kA
F1 > 250A gG
F1 ≤ 315A gG
F1 > 315A gG
F2 ≤ 250A gG
F2 not needed
F2 ≤ 315A gG
100A — 125A
160A — 200A
>250A
>315A
≤ 250A
≤ 315A
-
-
2
2
2
25mm
25mm
25mm
25 / 35mm
2
2
2
16mm
16mm
16mm
25mm
Unplugged
ON
OFF
PH2 / SLOT ¼
39.9 lnf∙in [4.5Nm]
Green: OK
Not Green: Replace Plug
inches
[mm]
2
2
Red
Green
ON
Plug replacement
Remote signalization
A.C.
250V / 1A
125V / 1A
Green
RC contact(s) states
SPD modules(s) functional / installation is protected
SPD module(s) unplugged or non-functional /
installation is unprotected
OFF
Step 1:
Unlock
D.C.
48V / 0.5A
24V / 0.5A
12V / 0.5A
11- 12
11-14
Closed
Open
Open
Closed
Step 2:
Pull module out