Galletti MYCOMFORT MEDIUM Manual Del Usuario página 20

Mando lcd para terminales
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 54
MYCOMFORT MEDIUM
PARAMETER CONFIGURATION PROCEDURE
> use keys
to change the value
> Press
to save the new value setting or
> After completing the modification of the parameters concerned press key
G B
to exit the procedure
NB: the parameter configuration phase is of limited duration. Once a certain time
has elapsed (around 2 minutes) the thermostat will switch back into the
Off status and only the saved changes will be retained.
AVAILABLE CONFIGURATIONS (PARAMETER P00)
The LCD controller can be configured in various ways according to the type of system.
Various configurations can be obtained through the P00 parameter (see configuration
procedure of controller parameters).
001
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed: 3
> Summer/winter switching logic: LOCAL MANUAL
002
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed: 3
> Summer/winter switching logic: REMOTE MANUAL
003
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed: 3
> Summer/winter switching logic: AUTOMATIC WATER SIDE
004
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed : 4
> Summer/winter switching logic: LOCAL MANUAL
005
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed: 4
> Summer/winter switching logic: REMOTE MANUAL
006
> System pipes: 2
> Valve: NO
> Heating element: NO
> Fan speed: 4
> Summer/winter switching logic: AUTOMATIC WATER SIDE
FC66002605 - rev. 02
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
007
> System pipes: 2
to cancel the modification
> Valve: NO
> Heating element: YES
> Fan speed: 3
> Summer/winter switching logic: LOCAL MANUAL
008
> System pipes: 2
> Valve: NO
> Heating element: YES
> Fan speed: 3
> Summer/winter switching logic: REMOTE MANUAL
009
> System pipes: 2
> Valve: NO
> Heating element: YES
> Fan speed: 3
> Summer/winter switching logic: AUTOMATIC AIR SIDE
010
> System pipes: 2
> Valve: NO
> Heating element: YES
> Fan speed: 4
> Summer/winter switching logic: LOCAL MANUAL
0 1 1
> System pipes: 2
> Valve: NO
> Heating element: YES
> Fan speed: 4
> Summer/winter switching logic: REMOTE MANUAL
012
> System pipes: 2
> Valve: NO
> Heating element: YES
> Fan speed: 4
> Summer/winter switching logic: AUTOMATIC AIR SIDE
013
> System pipes: 2
> Valve: 2-3 WAYS
> Heating element: NO
> Fan speed: 3
> Summer/winter switching logic: LOCAL MANUAL
014
> System pipes: 2
> Valve: 2-3 WAYS
> Heating element: NO
> Fan speed: 3
> Summer/winter switching logic: REMOTE MANUAL