Loop Wire Material - Allmatic A1H-U Manual De Instrucciones

Ocultar thumbs Ver también para A1H-U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

When installing multiple turns in the loop, it is recommended to place the wires like shown in figure
below.
4-5 mm
Road surface
Loop with multiple turns
The recommended groove depth is 30-50 mm (1.2-2.0 inches). If the wires are installed deeper than
50 mm (2.0 inches), the detection signal for the Loop Detector is reduced and detection of high bed
vehicles can be compromised.
It is possible to create the loop using a single multi-conductor cable by soldering the individual conductors
in series like shown in figure above. In the example shown, the 4-conductor cable creates a loop with
4 turns. If this approach is used, it is important to protect the soldered joints against any moisture with
adhesive-lined heat shrink tubing or equivalent.
Note: A common problem for loop failures is wire splicing. It is recommended to use one continuous
wire without any splices. If wire splicing is used, the wires must be soldered. Screw or spring terminals
are not allowed. All wire splices must be insulated against moisture with adhesive-lined heat shrink
tubing or equivalent.

7.3. Loop wire material

It is important to select the right type of cable for the loop wire. If insulating material is not suitable
for the application, the cable jacket can crack or absorb moisture. It is a common problem to have
moisture penetration in the cable jacket, which can cause a wire shorting to ground. This can lead to
conditions where the application works well while it is dry, but starts failing in high humidity conditions
or rain. A cracked cable insulation can lead to similar issues.
Cable recommendations:
• Wire insulating material of Cross Linked Polyethylene is recommended for both cold and hot sealant.
• Wire insulating material of polyvinyl chloride (PVC) is only recommended for hot sealant and if the
wires are encapsulating completely. Otherwise, PVC insulating material is not advised.
• It is important to avoid any voids in the sealing around the cable. This can allow moisture to build
up and cause loop failures.
To troubleshoot broken wires an insulation tester (500 MΩ minimum) can be used. Place one wire from
the meter to the disconnected wire loop and place the other meter wire in the ground. Testing should
be performed with AC voltage.
Measured resistance
100 to 1000 MΩ
50 to 100 MΩ
0 to 50 MΩ
16
Rev.00 - 09.2021 | A1H-U Single Loop Detector | © 2021 | Allmatic
Loop sealant
Loop wire
Loop wire 2
= Solder joints
Soldering of a single multi-conductor cable
Conclusion
Loop condition is good
Loop integrity is questionable
Loop needs to be replaced
Loop wire 1

Publicidad

Tabla de contenido
loading

Tabla de contenido