Viessmann SI 1830 Manual Del Usuario página 10

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
EN
Characteristics:
Mains supply
Max. discharge head
Operating time
Noise level in application
Water levels
Max. condensate temperature & acidity
Reservoir volume
Protection
Pump dimensions
SAFETY INSTRUCTIONS
- This pump is only intended for pumping water.
- This pump is only intended for indoor use. The pump may
not be used as an immersion pump. The pump and the
entire supply hose must be protected from frost.
- This device may not be used by persons (including child-
ren) with restricted physical, sensory or mental capacities
are supervised by a person responsible for their safety or
have been taught how to use the device by this person.
- Children should be supervised to ensure that they do not
play with the device.
- All malfunctions and in particular damage to the power
to preclude any risk.
- In accordance with the installation instructions, on mo-
dels that are not connected to a power socket, permanently
installed cables must include a device for disconnecting
the equipment from the power supply.
WARNING: Risk of electric shock: This pump has an earth
cable. Check that the cable is earthed to minimise the risk
of electric shock.
1/ COMMISSIONING
a/ Power supply
b/ Electrical connection of the safety contact
on site.
PLEASE NOTE
The recommended connection in accordance with the Fig.
11a and 11b would switch off the mains power to the boiler
control unit. In this case, the heat supply, the frost protec-
tion monitoring and any system monitors are disabled.
The recommended connection in accordance with Fig. 11c
If the external EA1 extension module is connected to the
boiler, the alarm connection can be connected potential-
free to the digital input. In this case, the alarm contact of
the condensate pump must be connected as a N/O contact.
See EA1 installation instructions for connection.
Plug 96 offers a further option for connecting the safety
contact.
For this, observe the installation instructions / safety ins-
tructions of the respective equipment.
10
N1062_00_1546.indd 10
230V~ 50Hz - 75 W – 0.80A
400 l/h
3.7m
0.5 l
IP X4
L 190x l 80x H 100mm
c/ Hydraulic connection
The pump is mounted in a horizontal plane below the ap-
pliance condensate drain (Fig. 4). An opening (24 mm dia.)
is provided in the cover which acts as a condensate inlet.
Condensate is pumped via a non-return valve to which a
hose (10 mm max. internal diameter) must be connected
with a maximum permissible radius of 50 mm (Fig. 10). The
non-return valve can simply be undone before the pressure
d/ Siting/installation
The pump can be mounted in its container (Fig. 8) or in a
pan with a maximum height of 70 mm (Fig. 7).
consideration the pressure drop values.
2/ COMMISSIONING
a/ Function test
%: 1 s ON / 5 s OFF or 2 s ON / 38 s OFF.
-
b/ Cleaning
another function test for pump and alarm.
PLEASE NOTE: Always switch off the pump off before
-
cleaning.
3/ SAFETY
- The safety function contact provides protection against the
temperature at 120 °C.
- Self-extinguishing casing
4/ WARRANTY
24 months from the date of delivery. Covering all concealed
incorrect maintenance and force majeure.
The guarantee is restricted to the replacement of the defective
Vertical
Total tubing length
discharge
5 m
10 m
head
0
400
340
1
320
270
2
240
200
3
150
110
50
40
4
0
0
20 m
30 m
250
200
190
150
130
100
70
50
25
15
0
0
-
-
-
-
10/11/2015 11:57:53

Publicidad

Tabla de contenido
loading

Tabla de contenido