Input Power And Motor Cable Stripping Lengths - Eaton PowerXL DH1 VFD Serie Instrucciones De Montaje

Tabla de contenido

Publicidad

PowerXL DH1 Series VFD

Input power and motor cable stripping lengths

Power Wiring in Inches (mm)
Frame
Size
A1
B1
FR0
0.39
5.12
(10)
(130)
FR1
0.39
1.77
(10)
(45)
FR2
0.59
1.77
(15)
(45)
FR3
0.59
1.57
(15)
(40)
FR4
0.98
2.56
(25)
(65)
FR5
1.10
6.10
(28)
(155)
FR6
0.98
4.72
(25)
(120)
Power connection tightening torque
Frame
Power wire
Size
in-lb (Nm)
FR0
5.3 (0.6)
FR1
5.3 (0.6)
FR2
15.6 (1.8)
FR3
40 (4.5)
FR4
95 (10.7)
FR5
354 (40.0)
FR6
480 (54.2)
Notes
Strip the motor and power cables as shown above.
®
Both UL
and IEC tools may be used.
Applies to strained wire, solid wire, or ferrule installations.
FR0 is not available till June 2018.
Motor Wiring in Inches (mm)
C1
D1
A2
0.39
5.12
0.39
(10)
(130)
(10)
0.39
1.38
0.39
(10)
(35)
(10)
0.59
1.77
0.59
(15)
(45)
(15)
0.59
1.97
0.59
(15)
(50)
(15)
0.98
4.72
0.98
(25)
(120)
(25)
1.10
9.45
1.10
(28)
(240)
(28)
0.98
7.87
0.98
(25)
(200)
(25)
Ground wire
Control wire
in-lb (Nm)
in-lb (Nm)
14 (1.6)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
14 (1.6)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
B2
C2
D2
3.15
0.39
1.97
(80)
(10)
(50)
1.77
0.39
1.38
(45)
(10)
(35)
1.57
0.59
1.57
(40)
(15)
(40)
1.57
0.59
1.97
(40)
(15)
(50)
2.56
0.98
4.72
(65)
(25)
(120)
6.10
1.10
9.45
(155)
(28)
(240)
4.72
0.98
7.87
(120)
(25)
(200)
Instruction Leaflet IL040029EN
Effective December 2017
EATON
www.eaton.com
13

Publicidad

Tabla de contenido
loading