DuroZone
INSTALLATION INSTRUCTIONS
Model OSL - Occupancy Sensor
For use with DuroZone RCD Round Diffuser Damper
Installation Directly in Wall
Plastic Wall Anchor
Cutout in Wall - see template
Wiring the Occupancy Sensor
to the RCD Diffuser Damper
A RCD damper and OSL Occupancy Sen-
sor are connected using the GND, VP and
+5V terminals.
To 24VAC
Transformer
Install all devices in accordance with applicable electrical and mechanical codes.
®
Use this
Template
for installing
OSL directly
into the wall.
Wiring One Occupancy Sensor to Control
Multiple RCD Dampers
An Occupancy Sensor can control multiple RCD dampers using
the VP and GND terminals. Up to six RCD dampers can be con-
trolled by one OSL Occupancy Sensor. The MIN to MAX range of
the OSL corresponds to the range from the minimum flow position
to fully open.
Model OSL
Occupancy
Sensor
IMPORTANT
Only the +5V terminal on one RCD damper is connected to the Occu-
pancy Sensor.
When using one transformer to power multiple motors, wire all 24 VAC
motor terminals to the same transformer terminal and all COM motor ter-
minals to the other transformer terminal. Damper Motors are rated 3.5VA
and 130 miliamps during operation; 2.25VA and 90 miliamps when idle.
Installation in Switch Box
To 24VAC
Transformer
2
Switch Box
Model OSL
Occupancy
Sensor