The main settings of the system are graphically summed up on the Home Page.
Home Page
The icon at top left indicates the type of regulation selected.
The icon at centre top indicates the operating mode selected (auto or economy).
The icon at top right indicates the presence of a single
The rotation of the icon
At the centre of the Home Page is a read-only parameter which can be chosen from
a small set of parameters on Page 9.0 of the menu.
From the Home Page it is possible to access the page for regulating the contrast
of the display: hold down the hidden button, then press and release the right button.
EVOPLUS circulators offer 2 menus: user menu and advanced menu. The user
menu is accessible from the Home Page by pressing and releasing the central
"Menu" button.
The user menu is accessible from the Home Page by holding down the central
"Menu" button for 5 seconds.
Page 1.0
The factory settings are set from Page 1.0 by holding down the left and right
buttons at the same time for 3 seconds.
The resetting of the factory settings will be notified by the appearance of the
symbol
The regulating mode is set from Page 2.0. You can choose between the following
Page 2.0
modes:
Page 2.0 displays 3 icons which represent:
ENGLISH
or
next to the word "Default".
1.
= Proportional differential pressure regulation.
2.
= Proportional differential pressure regulation with set-point set by
external signal (0-10V or PWM).
3.
= Proportional differential pressure regulation with set-point
depending on temperature with positive increment.
4.
= Proportional differential pressure regulation with set-point
depending on temperature with negative increment.
5.
= Regulation with constant differential pressure.
6.
= Constant differential pressure regulation with set-point set by
external signal (0-10V or PWM).
7.
= Constant differential pressure regulation with set-point depending
on temperature with positive increment.
8.
= Constant differential pressure regulation with set-point depending
on temperature with negative increment.
9.
= Regulation with constant curve with rotation speed set from the
display.
10.
= Regulation with constant curve with rotation speed set by an
external signal (0-10V or PWM).
central icon = setting currently selected
right icon = next setting
left icon = previous setting
indicates which circulation pump is operating.
or twin inverter
.