Tab. 5-2
MCA: minimum circuit amps (A)
MFA: maximum fuse amps (A)
IFM: indoor fan motor
KW: rated motor output (kW)
FLA: Full load current at max admissible conditions (A)
Select the wire diameters (minimum value) individually for each unit based on
the table 7.2.
Maximum allowable voltage range variation between phases is 2%
Select circuit breaker that having a contact separation in all poles not less than
3mm providing full disconnection.
The MFA is used to select the current circuit breakers and residual current
operation breakers.
18-1