End Of Programming; Delivery Includes - Phoenix Contact MCR-SL-D-U/I Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.11 End of programming

5. Connections
1
10-30 VDC
2
GND 1
3
GND 1
4
Latch
5
I
6
GND 2
7
U
6. Technical data
Anzeige: Display:
5digit 7 segment red
LED-Display,
8 mm high characters
Range of input signals
0 .. 10 V DC
2 .. 10 V DC
0 .. 20 mA DC
4 .. 20 mA DC
Accuracy:
< 0.1% ± 1 digit at an ambient tempe-
rature of 20 °C
Zero adjustment:
automatic
Temperature drift:
<70ppm/K
Measuring rate:
0,5 Measurement/sec ...
2 Measurement/sec
Current measuring:
Voltage drop:
max. 2,0 V at 20 mA
Current limitation: 50 mA
Programming routine will
be passed through once
again. All parameters can
be checked.
Programming routine will
be left and the new pa ra -
me ters will be stored. Af ter -
wards the device is ready
to use.
Voltage measurement:
Input resistance: >1 MW
Elimination of power line hum:
digital filter at 50 Hz
Supply voltage
:
10...30 VDC,
galvanically isolated
Current consumption:
max. 50 mA
Ambient temperature:
-10°C ... +50°C
Storage temperature:
-25°C ... +70°C
Data retention:
via EEPROM 1 Mio.
memory cycles or 10 years
Weight:
ca. 50 g
Protection:
IP 65 (front)
EMC:
Noise emission:
Noise immunity:
Cleaning:
The front of the unit is only to be cleaned with a soft
wet (water !) cloth.
Error messages:
Err 0*
Error/defect in A/D-part
Err 3*
Error/defect EEPROM
Err 4**
Analogue input overflow
Err 5*
Error/defect EEPROM. Device not cali-
brated
* Please send the device back for checking
** Please check input signal and programming

7. Delivery includes:

- Digital display with analogue inputs
- Panel mounting clip
- Bezel for screw mount, panel cut-out
50x25 mm
- Bezel for clip mount, panel cut-out
50x25 mm
- Sealing
- Tack dry symbols
EN 55 011 Class B
EN 61 000-6-2
11

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

2864011-02

Tabla de contenido